Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
25…7945 scfh 0.4…132.4 scfm 1.2…340.2 ft/s
Process connection threaded connection 1″ NPT DN25
Application
Application for industrial applications
Media compressed air
Medium temperature [°C] -10…60
Min. bursting pressure [psi] 928
Pressure rating [psi] 232
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 80
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 1
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputs counter reset
Outputs
Output signal switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 150; (per output)
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable)
Max. load [Ω] 500
Pulse output consumed quantity meter
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
25…7945 scfh 0.4…132.4 scfm 1.2…340.2 ft/s
Display range
0…9535 scfh 0…158.9 scfm 0…408.2 ft/s
Resolution
5 scfh 0.1 scfm 0.2 ft/s
Set point SP
69…7943 scfh 1.1…132.4 scfm 3…340.1 ft/s
Reset point rP
30…7904 scfh 0.5…131.7 scfm 1.3…338.4 ft/s
Analogue start point ASP
0…6357 scfh 0…105.9 scfm 0…272.2 ft/s
Analogue end point AEP
1589…7946 scfh 26.5…132.4 scfm 68…340.2 ft/s
Low flow cut-off LFC
9…85 scfh 0.2…1.4 scfm 0.4…3.6 ft/s
In steps of
1 scfh 0.1 scfm 0.1 ft/s
Pressure monitoring
Measuring range [psi] -15…232
Display range [psi] -15…290
Resolution [psi] 1
Set point SP [psi] -13…232
Reset point rP [psi] -15…231
Analogue start point [psi] -15…186
Analogue end point [psi] 32…232
In steps of [psi] 1
Volumetric flow quantity monitoring
Measuring range
0…100000000 m³ 0…353146667.2 scf
Display range
0…100000000 m³ 0…353146667.2 scf
Set point SP
0.001…10000000 m³ 0.05…353146667.2 scf
Pulse value
0.001…10000000 m³ 0.05…353146667.2 scf
In steps of
0.0001 m³ 0.005 scf
Pulse length [s] 0.007…2
Temperature monitoring
Measuring range
-10…60 °C 14…140 °F
Display range
-24…74 °C -11.2…165.2 °F
Resolution
0.2 °C 0.5 °F
Set point SP
-9.7…60 °C 14.6…140 °F
Reset point rP
-10…59.7 °C 14…139.4 °F
Analogue start point
-10…46 °C 14…114.8 °F
Analogue end point
4…60 °C 39.2…140 °F
In steps of
0.1 °C 0.1 °F
Accuracy / deviations
Temperature coefficient [1/K] ± 0,07 % MW
Accuracy (in the measuring range) class 141: ± (2 % MW + 0,5 % MEW); class 344: ± (6 % MW + 0,6 % MEW) ; air quality to ISO 8573-1:2010; at medium temperature 73 °F
Repeatability ± (0,4 % MW + 0,1 % MEW)
Pressure monitoring
Repeatability [% of the final value] ± 0,2
Characteristics deviation [% of the final value] < ± 0,5; (BFSL = Best Fit Straight Line)
Greatest TEMPCO of the span [% MEW / 10 K] ± 0,15
Greatest TEMPCO of the zero point [% MEW / 10 K] ± 0,25
Temperature monitoring
Accuracy [K] ± 0,5; (medium flow in the limit area of the flow measurement range)
Response times
Response time [s] 0.1; (dAP = 0)
Damping for the switching output dAP [s] 0…5
Pressure monitoring
Response time [s] 0.05
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 0,5
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; current/pulse output; display can be rotated and switched off; Display unit; totaliser
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles Digital Measuring Sensor (0x800A), Identification and Diagnosis (0x4000)
SIO mode yes
Required master port type A
Process data analogue 8
Process data binary 2
Min. process cycle time [ms] 7.2
Supported DeviceIDs
Type of operation DeviceID
Default 867
Operating conditions
Ambient temperature [°F] 32…140
Storage temperature [°C] -4…185
Max. relative air humidity [%] 90
Protection IP 65; IP 67
Mechanical data
Weight [g] 1613
Materials PBT+PC-GF30; PPS GF40; stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); steel (1.5523) galvanised; 2.0401 (brass / CW614N); FKM
Materials (wetted parts) stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); FKM; ceramics glass passivated; PPS GF40; Al2O3 (ceramics); acrylate
Process connection threaded connection 1″ NPT DN25
Displays / operating elements
Display
colour display 1,44″, 128 x 128 pixels
2 x LED, yellow
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533.
For information about installation and operation please see the operating instructions.
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12

Thông tin bổ sung

Thương hiệu
Thời gian bảo hành

5 Năm

Điện áp ngõ vào
Ngõ ra

Analog, NC, NO, NPN, PNP

Yêu cầu tư vấn0342 678 887(Call/Zalo)

Khu vực Miền Nam

Call: 0345 177 768 / Chat Zalo zalo

Khu vực Miền Bắc

Call: 0384 988 968 / Chat Zalo zalo

Khu vực Miền Trung

Call: 0374 687 899/ Chat Zalo zalo

Dịch vụ kỹ thuật/Bảo hành

Call: 0348 957 778/ Chat Zalo zalo

Email liên hệ

dich-vu-sua-chua-bien-tan-thiet-bi-tu-dong-hoa