Model | KV-C64XB | |||
Type | Input unit | |||
External connection mode | Connector (MIL standard)*1 | |||
Input | Number of inputs | 64 points | ||
Input mode | DC 24 V mode*2 | |||
Max. input voltage | DC 26.4 V (±10 %) | |||
Rated input voltage | DC 24 V, 4.1 mA | |||
Min. ON voltage | 19 V | |||
Max. OFF current | 1.5 mA | |||
Common point mode | 32 points/1 common (4 terminals)*3 | |||
Input time constant | [Constant at input setting 25µs] OFF to ON: TYP 25 µs/MAX 65 µs、ON to OFF: TYP 75 µs/MAX 120 µs [Constant at input setting 1 ms] OFF to ON: TYP 1 ms/MAX 1.2 ms、ON to OFF: TYP 1 ms/MAX 1.2 ms [Constant at input setting 10 ms] OFF to ON: TYP 10 ms/MAX 12 ms、ON to OFF: TYP 10 ms/MAX 12 ms (switchable among 3 levels) |
|||
Input impedance | 5.6 kΩ | |||
Internal current consumption | 25 mA or less | |||
Weight | Approx. 140 g | |||
*1 In conformity with MIL-C-83503. *2 2-wire type supported on all terminals (not supported on 2-wire type proximity sensor EV series) *3 Although the KV-C64XA/C64XB has 4 COM points, internally there is an H-side (2 points) and an L-side (2 points) that share a common circuit. |