| Technical data | BK2000 |
|---|---|
| Number of Bus Terminals | 64 |
| Max. number of bytes fieldbus | 512 byte input and 512 byte output |
| Digital peripheral signals | 512 inputs/outputs |
| Analog peripheral signals | 128 inputs/outputs |
| Configuration possibility | via KS2000 or the controller |
| Bus interface | 2 x standard fibre optic connector Z1000 (plastic fibre), Z1010 (HCS fibre) |
| Power supply | 24 V DC (-15 %/+20 %) |
| Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
| Starting current | approx. 2.5 x continuous current |
| Recommended fuse | ? 10 A |
| Current supply K-bus | 1750 mA |
| Power contacts | max. 24 V DC/max. 10 A |
| Electrical isolation | 500 V (power contact/supply voltage) |
| Distance between stations | 45 m for APF fibre, 300 m HCS fibre |
| Weight | approx. 150 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Approvals/markings | CE, UL, ATEX |
| Ex marking | II 3 G Ex nA IIC T4 Gc |