Technical data | KL3208-0010 |
---|---|
Number of inputs | 8 |
Power supply | via the K-bus |
Technology | 2-wire |
Sensor types | Pt1000 (default), Ni1000, resistor/potentiometer 6/65/655 k?, NTC 1.8 k/2.2 k/3 k/5 k/10 k/20 k/100 k |
Connection method | 2-wire |
Measuring range | -50…+150 °C (depending on sensor type) |
Conversion time | ~ 1 s |
Measuring current | typ. < 0.5 mA |
Resolution | 0.01 °C per digit |
Measuring error | -20…+60 °C: ±0.25 °C at 25 °C ambient temperature; -50…+150 °C: ±1.5 °C (for Pt/Ni sensors) |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | – |
Current consumption K-bus | typ. 85 mA |
Bit width in the process image | input: 8 x 16 bit data (8 x 8 bit control/status optional) |
Configuration | no address setting, configuration via Bus Coupler or controller |
Conductor types | solid wire, stranded wire and ferrule |
Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver |
Rated cross-section | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² |
Special features | open-circuit recognition, cable resistance calibration, particularly suitable for building automation |
Weight | approx. 75 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |