| Model | DL-PD1 | |||
| Sensorconnectionspecifications | Connectablesensors | Sensor amplifiers with D-bus support*1 | ||
| Number ofconnectablesensor units | 15 units max.*2 | |||
| PROFIBUSDPspecifications | Device type | DP-V1 Slave (D-sub 9 pin, Number of the ports: 1) | ||
| Communication speed | 9.6 kbit/s to 12 Mbit/s | |||
| Cable length | 9.6 / 19.2 / 45.45 / 93.75 kbit/s : 1200 m187.5 kbit/s : 1000 m500 kbit/s : 400 m1.5 Mbit/s : 200 m3 / 6 / 12 Mbit/s : 100 m | |||
| Power voltage | 20 to 30 VDC, including ripple (p-p) 10%(This voltage is supplied from the connected sensor amplifier.) | |||
| Power consumption | 1600 mW or less (65 mA max. at 24 V) | |||
| Environmental resistance | Ambient temperature | -20 to +55 °C (No freezing) | ||
| Relative humidity | 35 to 85 % RH (No condensation) | |||
| Vibration resistance | 10 to 55 Hz, Double amplitude 1.5 mm, 2 hours in each of the X, Y, and Z directions | |||
| Shock resistance | 500 m/s2, 3 times in each of the X, Y, and Z directions | |||
| Material | Main unit case and dust cover: Polycarbonate PROFIBUS connector: Steel – Nickel plating | |||
| Weight | Approx. 65 g | |||
| *1 “D-bus” is the name of KEYENCE’s wiring-saving system for sensor amplifiers.*2 Varies with the sensor amplifiers connected. | ||||
khối giao tiếp Keyence DL-PD1
PROFIBUS DP Compatible Communication Unit
SKU: DL-PD1
Nhà Sản Xuất: Keyence
Bảo hành: Chính hãng
Chứng từ: CO/CQ, hóa đơn VAT

Thông tin bổ sung
| Thương hiệu | |
|---|---|
| Thời gian bảo hành | 1 Năm |