|  Product characteristics | 
|---|
|  Output signal |  switching signal | 
|  Measuring range | |  0…100 bar |  0…1450 psi |  0…10 MPa |  
  | 
|  Process connection |  threaded connection 1/4″ NPT internal thread | 
|  Application | 
|---|
|  Application |  for industrial applications | 
|  Media |  liquids and gases | 
|  Conditionally suitable for |  use in gases at pressures > 25 bar only on request | 
|  Medium temperature [°C] |  -25…80 | 
|  Min. bursting pressure |  | 
|  Pressure rating |  | 
|  Type of pressure |  relative pressure | 
|  Electrical data | 
|---|
|  Operating voltage tolerance [%] |  5…10 | 
|  Operating voltage [V] |  85…265 AC | 
|  Nominal voltage AC [V] |  < 250 | 
|  Current consumption [mA] |  < 10 | 
|  Min. insulation resistance [MΩ] |  100; (500 V DC) | 
|  Protection class |  II | 
|  Reverse polarity protection |  no | 
|  Power-on delay time [s] |  0.2 | 
|  Integrated watchdog |  yes | 
|  Inputs / outputs | 
|---|
|  Number of inputs and outputs |  Number of digital outputs: 1 | 
|  Outputs | 
|---|
|  Total number of outputs |  1 | 
|  Output signal |  switching signal | 
|  Electrical design |  Triac | 
|  Number of digital outputs |  1 | 
|  Output function |  normally open / normally closed; (parameterisable) | 
|  Max. voltage drop switching output AC [V] |  2 | 
|  Permanent current rating of switching output AC [mA] |  250; ((…70 °C) 1000 (…60 °C) 1500 (…45 °C) 2500 (…20 °C)) | 
|  Switching frequency AC [Hz] |  < 160 | 
|  Short-circuit proof |  no | 
|  Overload protection |  no | 
|  Measuring/setting range | 
|---|
|  Measuring range | |  0…100 bar |  0…1450 psi |  0…10 MPa |  
  | 
|  Set point SP | |  1…99.9 bar |  10…1450 psi |  0.1…9.99 MPa |  
  | 
|  Reset point rP | |  0.5…99.5 bar |  10…1440 psi |  0.05…9.95 MPa |  
  | 
|  In steps of |  | 
|  Accuracy / deviations | 
|---|
|  Switch point accuracy [% of the span] |  < ± 1,0 | 
|  Repeatability [% of the span] |  < ± 0,1; (with temperature fluctuations < 10 K) | 
|  Linearity deviation [% of the span] |  < ± 0,5 | 
|  Hysteresis deviation [% of the span] |  < ± 0,1 | 
|  Long-term stability [% of the span] |  < ± 0,1; (per year) | 
|  Temperature coefficient zero point [% of the span / 10 K] |  < ± 0,2; (-25…80 °C) | 
|  Temperature coefficient span [% of the span / 10 K] |  < ± 0,3; (-25…80 °C) | 
|  Response times | 
|---|
|  Delay time programmable dS, dr [s] |  0, 0,2,…10, 11,…50 | 
|  Damping for the switching output dAP [s] |  0…4 | 
|  Software / programming | 
|---|
|  Adjustment of the switch point |  programming button | 
|  Parameter setting options |  hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit | 
|  Operating conditions | 
|---|
|  Ambient temperature [°C] |  -25…80 | 
|  Storage temperature [°C] |  -40…100 | 
|  Protection |  IP 67 | 
|  Mechanical data | 
|---|
|  Weight [g] |  391 | 
|  Materials |  stainless steel (1.4301 / 304); PC; PBT; PA; FKM | 
|  Materials (wetted parts) |  stainless steel (1.4305 / 303); ceramics; FKM | 
|  Min. pressure cycles |  100 million | 
|  Process connection |  threaded connection 1/4″ NPT internal thread | 
|  Restrictor element integrated |  no (can be retrofitted) | 
|  Displays / operating elements | 
|---|
|  Display | |  switching status |  LED, red |  |  function display |  7-segment LED display |  |  measured values |  7-segment LED display |  
  | 
|  Electrical connection | 
|---|
|  Required protection |  miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting | 
|  Remarks | 
|---|
|  Remarks |  | 
|  Pack quantity |  1 pcs. | 
|  Electrical connection | 
|---|
|  Connection |  Connector: 1 x 1/2″ |