Product characteristics |
---|
Output signal | switching signal |
Measuring range | -1…1 bar | -1000…1000 mbar | -30…30 inHg | -100…100 kPa |
|
Process connection | threaded connection 1/4″ NPT internal thread |
Application |
---|
Application | for industrial applications |
Media | liquids and gases |
Medium temperature [°C] | -25…80 |
Min. bursting pressure | 50 bar | 1476 inHg | 5000 kPa |
|
Pressure rating | |
Type of pressure | relative pressure; vacuum |
Electrical data |
---|
Operating voltage tolerance [%] | 5…10 |
Operating voltage [V] | 85…265 AC |
Nominal voltage AC [V] | < 250 |
Current consumption [mA] | < 10 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | II |
Reverse polarity protection | no |
Power-on delay time [s] | 0.2 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 1 |
Outputs |
---|
Total number of outputs | 1 |
Output signal | switching signal |
Electrical design | Triac |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output AC [V] | 2 |
Permanent current rating of switching output AC [mA] | 250; ((…70 °C) 1000 (…60 °C) 1500 (…45 °C) 2500 (…20 °C)) |
Switching frequency AC [Hz] | < 160 |
Short-circuit proof | no |
Overload protection | no |
Measuring/setting range |
---|
Measuring range | -1…1 bar | -1000…1000 mbar | -30…30 inHg | -100…100 kPa |
|
Set point SP | -0.97…1 bar | -29…30 inHg | -97…100 kPa |
|
Reset point rP | -0.99…0.98 bar | -30…29 inHg | -99…98 kPa |
|
In steps of | |
Accuracy / deviations |
---|
Switch point accuracy [% of the span] | < ± 1,0 |
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Linearity deviation [% of the span] | < ± 0,5 |
Hysteresis deviation [% of the span] | < ± 0,1 |
Long-term stability [% of the span] | < ± 0,1; (per year) |
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-25…80 °C) |
Temperature coefficient span [% of the span / 10 K] | < ± 0,3; (-25…80 °C) |
Response times |
---|
Delay time programmable dS, dr [s] | 0, 0,2,…10, 11,…50 |
Damping for the switching output dAP [s] | 0…4 |
Software / programming |
---|
Adjustment of the switch point | programming button |
Parameter setting options | hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit |
Operating conditions |
---|
Ambient temperature [°C] | -25…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 65 |
Mechanical data |
---|
Weight [g] | 389 |
Materials | stainless steel (1.4301 / 304); PC; PBT; PA; FKM |
Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM |
Min. pressure cycles | 100 million |
Process connection | threaded connection 1/4″ NPT internal thread |
Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements |
---|
Display | switching status | LED, red | function display | 7-segment LED display | measured values | 7-segment LED display |
|
Electrical connection |
---|
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting |
Remarks |
---|
Remarks | |
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x 1/2″ |