| Product characteristics |
|---|
| Output function | normally open |
| Sensing range [mm] | 15 |
| Housing | threaded type |
| Dimensions [mm] | M30 x 1.5 / L = 81 |
| Application |
|---|
| Installation | use in hazardous areas only with installed protective cover |
| Electrical data |
|---|
| Operating voltage [V] | 20…250 AC/DC |
| Protection class | II |
| Reverse polarity protection | yes |
| Outputs |
|---|
| Output function | normally open |
| Max. voltage drop switching output DC [V] | 6 |
| Max. voltage drop switching output AC [V] | 6.5 |
| Minimum load current [mA] | 5 |
| Max. leakage current [mA] | 2.5 (250 V AC) / 1.3 (130 V AC) / 0.8 (24 V DC) |
| Permanent current rating of switching output AC [mA] | 150 |
| Permanent current rating of switching output DC [mA] | 100 |
| Short-time current rating of switching output [mA] | 2200; (20 ms / 0,5 Hz) |
| Switching frequency AC [Hz] | 25 |
| Switching frequency DC [Hz] | 50 |
| Notes on switching frequency | | only for resistive loads; 2 Hz for utilisation category AC-140 |
|
| Short-circuit protection | no |
| Overload protection | no |
| Detection zone |
|---|
| Sensing range [mm] | 15 |
| Real sensing range Sr [mm] | 15 ± 10 % |
| Operating distance [mm] | 0…12.1 |
| Accuracy / deviations |
|---|
| Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
| Hysteresis [% of Sr] | 1…20 |
| Switch point drift [% of Sr] | -10…10 |
| Operating conditions |
|---|
| Ambient temperature [°C] | -20…60 |
| Protection | IP 67 |
| Mechanical data |
|---|
| Weight [K40] | 489 |
| Housing | threaded type |
| Mounting | non-flush mountable |
| Dimensions [mm] | M30 x 1.5 / L = 81 |
| Thread designation | M30 x 1.5 |
| Materials | brass white bronze coated; sensing face: PBT; lock nuts: brass white bronze coated; Protective cover: PA |
| Displays / operating elements |
|---|
| Display | | switching status | 1 x LED, yellow |
|
| Electrical connection |
|---|
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
| Accessories |
|---|
| Accessories (supplied) | | lock nuts: 3 | | Protective cover: 1 |
|
| Remarks |
|---|
| Remarks | | Recommendation: Check the safe functioning of the unit after a short circuit. |
|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | Cable: 6 m, PVC; 2 x 0.50 mm² |