Electrical data |
---|
Operating voltage [V] | 26.5…31.6 DC |
Max. current consumption from AS-i [mA] | 165 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital inputs: 2; Number of pneumatic outputs: 1 |
Inputs |
---|
Number of digital inputs | 2 |
Input circuit of digital inputs | PNP |
Sensor supply of the inputs | AS-i |
Voltage supply [V] | 20…30 |
Max. total current rating of inputs [mA] | 100 |
Input current High [mA] | > 3 |
Input current Low [mA] | < 1.5 |
Min. switching level high signal [V] | 10 |
Digital inputs protected against short circuits | yes |
Outputs |
---|
Electrical design | AS-i |
Number of pneumatic outputs | 1; (pneumatic NO/NC selectable output ; monostable) |
Operating conditions |
---|
Ambient temperature [°C] | 0…55 |
Note on ambient temperature | with special compressed air treatment: < 0 °C |
|
Protection | IP 67 |
AS-i classification |
---|
AS-i profile | S-3.F |
AS-i I/O configuration [hex] | 3 |
AS-i ID code [hex] | F |
AS-i certificate pending | yes |
Assignment of the data bits | data bit | D0 | D1 | D2 | D3 | Inputs / outputs | I-1 | I-2 | O-3 | not used |
|
Mechanical data |
---|
Weight [g] | 243 |
Type of mounting | screw mounting |
Materials | housing: PBT; metal parts: stainless steel (1.4305 / 303); Sealing: FKM |
Pneumatic system | 1 x 4/2-way seat valve |
Operating pressure range [bar] | 3…8 |
Operating pressure range [MPa] | 0.3…0.8 |
Note on working pressure range | incl. possible pressure peaks |
|
Air flow at 6/5 bar [l/min] | 500 |
Air flow at 6/0 bar [l/min] | 700 |
Permissible compressed air | filtered (5 µm); lubricated (ISO-VG10) or not lubricated |
Tube fittings | Legris LF 3000/8 |
Exhaust | exhaust can be discharged through tube connection |
Displays / operating elements |
---|
Display | operation | LED, green | function | LED, yellow |
|
Accessories |
---|
Accessories (optional) | |
Remarks |
---|
Remarks | Please see the notes on compressed air and EMC/ESD under “Downloads” |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | contact pins to module lower part, FK / PG: |