Electrical data |
---|
Operating voltage [V] | 26.5…31.6 DC; (“supply class 2” to cULus) |
Max. current consumption from AS-i [mA] | 230 |
Max. current load total [A] | 0.18 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital inputs: 2; Number of digital outputs: 2 |
Inputs |
---|
Number of digital inputs | 2 |
Input circuit of digital inputs | PNP |
Sensor supply of the inputs | AS-i |
Voltage supply [V] | 18…30 |
Max. total current rating of inputs [mA] | 180; (current load for all inputs and outputs: 180 mA) |
Min. switching level high signal [V] | 11 |
Digital inputs protected against short circuits | yes |
Outputs |
---|
Number of digital outputs | 2 |
Voltage range DC [V] | 18…30 |
Max. current load per output [mA] | 180; (current load for all inputs and outputs: 180 mA) |
Short-circuit proof | yes |
Electrically separated | no |
Actuator supply switching outputs | AS-i |
Operating conditions |
---|
Ambient temperature [°C] | -25…60 |
Protection | IP 65; IP 67; IP 68 |
AS-i classification |
---|
AS-i version | 2.11; 3.0 |
Extended addressing mode possible | yes |
AS-i profile | S-B.A.E |
AS-i I/O configuration [hex] | B |
AS-i ID code [hex] | A.E |
AS-i certificate | 100901 |
Assignment of the data bits | data bit | D0 | D1 | D2 | D3 | input | – | – | 3 | 4 | socket | – | – | I-3 | I-4 | pin | – | – | 4 | 4 | Output | 1 | 2 | – | – | socket | O-1 | O-2 | – | – | pin | 4 | 4 | – | – |
|
Assignment of the parameter bits | parameter bit | Designation | | | | | | P0 | not used | | | | | | P1 | peripheral fault indication | : 1 | activated | / 0 | deactivated | | P2 | not used | | | | | | P3 | not used | | | | | |
|
Mechanical data |
---|
Weight [g] | 111 |
Type of mounting | backplane mounting |
Dimensions [mm] | 90.5 x 30 x 23.5 |
Materials | PBT |
Displays / operating elements |
---|
Display | switching status | LED, yellow | operation | LED, green | errors | LED, red |
|
Accessories |
---|
Accessories (supplied) | Label tags | Protective caps: 2 |
|
Accessories (optional) | Protective cap: M8, E73005 | Flat cable insulation displacement connector: 1 m, round cable, E70582 | Flat cable insulation displacement connector: M12, E70096 | DIN rail adapter:, E73006 |
|
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection – AS-i |
---|
| Connector: 1 x M12 |
Electrical connection – Inputs |
---|
| Connector: 2 x M8 |
Electrical connection – Outputs |
---|
| Connector: 2 x M8 |