| Electrical data |
|---|
| Operating voltage [V] | 26.5…31.6 DC |
| Max. current consumption from AS-i [mA] | 150 |
| Max. current load total [A] | 4 |
| Integrated watchdog | yes |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital inputs: 2; Number of digital outputs: 2 |
| Inputs |
|---|
| Number of digital inputs | 2 |
| Input circuit of digital inputs | PNP |
| Sensor supply of the inputs | AS-i |
| Voltage supply [V] | 18…30; (via flat cable) |
| Max. total current rating of inputs [mA] | 100 |
| Input current High [mA] | 6…10 |
| Input current Low [mA] | 0…2 |
| Min. switching level high signal [V] | 11 |
| Digital inputs protected against short circuits | yes |
| Outputs |
|---|
| Number of digital outputs | 2 |
| Circuit | PNP |
| Voltage range DC [V] | 15…30; (to PELV; via flat cable) |
| Max. current load per output [mA] | 2000; (utilisation category DC-13 (control of electromagnets): 40 W (IEC 60947-5-1)) |
| Short-circuit proof | yes |
| Electrically separated | yes |
| Operating conditions |
|---|
| Ambient temperature [°C] | -10…50 |
| Protection | IP 50 |
| AS-i classification |
|---|
| AS-i version | 2.11; 3.0 |
| AS-i addressing | addressing socket |
| Extended addressing mode possible | no |
| AS-i profile | S-3.0.E |
| AS-i I/O configuration [hex] | 3 |
| AS-i ID code [hex] | 0.E |
| AS-i certificate pending | yes |
| Assignment of the data bits | | data bit | D0 | D1 | D2 | D3 | | input | 1 | 2 | – | – | | socket | I-1 | I-2 | – | – | | pin | 2+4 | 2+4 | – | – | | Output | – | – | 3 | 4 | | socket | – | – | O-3/4 | O-3/4 O-4 | | pin | – | – | 4 | 2 4 |
|
| Mechanical data |
|---|
| Weight [g] | 241 |
| Type of mounting | AS-i flat cables directly connectable |
| Materials | PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
| Displays / operating elements |
|---|
| Display | | operation | LED, green | | errors | LED, red | | function | LED, yellow |
|
| Accessories |
|---|
| Accessories (supplied) | |
| Accessories (optional) | | Protective cap: M12, E73004 | | Impact protection housing:, E7000A |
|
| Remarks |
|---|
| Remarks | | Mechanical protection has to be implemented. | | Otherwise the unit must be installed together with the impact protection housing (E7000A). | | Inputs and outputs must be electrically isolated. | | Do not connect any of the following points to an external potential: | | I-, I+, I1, I2 | | The connections are electrically connected with the AS-i cable. |
|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| quick mounting technology for AS-i flat cable: ; three orientations possible |
| Electrical connection – Inputs |
|---|
| Connector: M12 |
| Electrical connection – Outputs |
|---|
| Connection | Connector: M12 |