| Electrical data | 
|---|
| Operating voltage [V] | 26.5…31.6 DC; (“supply class 2” to cULus) | 
| Max. current consumption from AS-i [mA] | 150 | 
| Max. current load total [A] | 4 | 
| Integrated watchdog | yes | 
| Inputs / outputs | 
|---|
| Number of inputs and outputs | Number of digital inputs: 2; Number of digital outputs: 2 | 
| Inputs | 
|---|
| Number of digital inputs | 2 | 
| Input circuit of digital inputs | PNP | 
| Sensor supply of the inputs | AS-i | 
| Voltage supply [V] | 18…30; (via flat cable) | 
| Max. total current rating of inputs [mA] | 100 | 
| Input current High [mA] | 6…10 | 
| Input current Low [mA] | 0…2 | 
| Min. switching level high signal [V] | 11 | 
| Digital inputs protected against short circuits | yes | 
| Outputs | 
|---|
| Number of digital outputs | 2 | 
| Circuit | PNP | 
| Voltage range DC [V] | 15…30; (to PELV; via flat cable) | 
| Max. current load per output [mA] | 2000; (utilisation category DC-13 (control of electromagnets): 40 W (IEC 60947-5-1)) | 
| Short-circuit proof | yes | 
| Electrically separated | yes | 
| Operating conditions | 
|---|
| Ambient temperature [°C] | -25…70 | 
| Protection | IP 67 | 
| AS-i classification | 
|---|
| AS-i version | 2.11; 3.0 | 
| AS-i addressing | addressing socket | 
| Extended addressing mode possible | yes | 
| AS-i profile | S-B.A.E | 
| AS-i I/O configuration [hex] | B | 
| AS-i ID code [hex] | A.E | 
| AS-i certificate pending | yes | 
| Assignment of the data bits | | data bit | D0 | D1 | D2 | D3 |  | input | – | – | 3 | 4 |  | socket | – | – | I-3/4 | I-3/4 I-4 |  | pin | – | – | 4 | 2 4 |  | Output | 1 | 2 | – | – |  | socket | O-1/2 | O-1/2 / O-2 | – | – |  | pin | 4 | 2 4 | – | – | 
 | 
| Mechanical data | 
|---|
| Weight [g] | 187.5 | 
| Type of mounting | AS-i flat cables directly connectable | 
| Materials | PA; piercing contacts: CuSn6 nickel-plated and tin-plated | 
| Displays / operating elements | 
|---|
| Display | | operation | LED, green |  | errors | LED, red |  | function | LED, yellow | 
 | 
| Accessories | 
|---|
| Accessories (supplied) |  | 
| Accessories (optional) | | Protective cap: M12, E73004 | 
 | 
| Remarks | 
|---|
| Remarks | | Inputs and outputs must be electrically isolated. |  | Do not connect any of the following points to an external potential: |  | L-, L+, I-3/4, I-4 |  | The connections are electrically connected with the AS-i cable. | 
 | 
| Pack quantity | 1 pcs. | 
| Electrical connection | 
|---|
|  | quick mounting technology for AS-i flat cable: ; three orientations possible | 
| Electrical connection – Inputs | 
|---|
| Connection | Connector: M12 | 
| Electrical connection – Outputs | 
|---|
| Connection | Connector: M12 |