| Electrical data |
|---|
| Operating voltage [V] | 26.5…31.6 DC; (“supply class 2” to cULus) |
| Max. current consumption from AS-i [mA] | 30 |
| Max. current load total [A] | 3 |
| Integrated watchdog | yes |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital inputs: 4; Number of digital outputs: 3 |
| Inputs |
|---|
| Number of digital inputs | 4 |
| Input circuit of digital inputs | PNP |
| Sensor supply of the inputs | AUX |
| Voltage supply [V] | 20…30; (via flat cable) |
| Max. total current rating of inputs [mA] | 1000 |
| Input current High [mA] | 6…10 |
| Input current Low [mA] | 0…2 |
| Min. switching level high signal [V] | 11 |
| Digital inputs protected against short circuits | yes |
| Outputs |
|---|
| Number of digital outputs | 3 |
| Circuit | PNP |
| Voltage range DC [V] | 20…30; (to PELV; via flat cable) |
| Max. current load per output [mA] | 1000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1)) |
| Short-circuit proof | yes |
| Electrically separated | yes |
| Operating conditions |
|---|
| Ambient temperature [°C] | -25…70 |
| Protection | IP 67 |
| AS-i classification |
|---|
| AS-i version | 2.11; 3.0 |
| AS-i addressing | addressing socket |
| Extended addressing mode possible | yes |
| AS-i profile | S-7.A.E |
| AS-i I/O configuration [hex] | 7 |
| AS-i ID code [hex] | A.E |
| AS-i certificate pending | yes |
| Assignment of the data bits | | data bit | D0 | D1 | D2 | D3 | | input | 1 | 2 | 3 | 4 | | socket | I-1/2 | I-1/2 I-2 | I-3/4 | I-3/4 I-4 | | pin | 4 | 2 4 | 4 | 2 4 | | Output | 1 | 2 | 3 | 4 | | socket | O-1/2 | O-1/2 O2 | O-3 | – | | pin | 4 | 2 4 | 4 | – |
|
| Assignment of the parameter bits | | parameter bit | Designation | | | | | | | P0 | not used | | | | | | | P1 | peripheral fault indication | : 1 | activated | * / 0 | deactivated | | | P2 | not used | | | | | | | P3 | not used | | | | | |
|
| Mechanical data |
|---|
| Weight [g] | 289.5 |
| Type of mounting | AS-i flat cables directly connectable |
| Materials | PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
| Displays / operating elements |
|---|
| Display | | operation | LED, green Voltage AUX > 7 V | | errors | LED, red AUX 15 V ± 2 V | | function | LED, yellow |
|
| Accessories |
|---|
| Accessories (supplied) | |
| Accessories (optional) | | Protective cap: M12, E73004 |
|
| Remarks |
|---|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| quick mounting technology for AS-i flat cable: ; three orientations possible |
| Electrical connection – Inputs |
|---|
| Connection | Connector: M12 |
| Electrical connection – Outputs |
|---|
| Connection | Connector: M12 |