|  Product characteristics | 
|---|
|  Number of inputs and outputs |  Number of digital outputs: 2 | 
|  Factory setting |  hydrous coolants; water; media similar to water | 
|  Probe length L [mm] |  264 | 
|  Application | 
|---|
|  Special feature |  Gold-plated contacts | 
|  Media |  hydrous coolants; oils; oil-based media; water; media similar to water | 
|  Dielectric constant of the medium |  > 2 | 
|  Cannot be used for |  extremely conductive media; adhering media; granulates; bulk material; acids; alkali; hygienic areas and electroplating applications | 
|  Maximum speed of the change of level [mm/s] |  100 | 
|  Tank pressure [bar] |  0.5; (when mounting with mounting accessories: E43001 – E43007, E43019) | 
|  Coolants | 
|---|
|  Medium temperature [°C] |  0…35; (with climatic tube E43100: 35…65 °C) | 
|  Oil | 
|---|
|  Medium temperature [°C] |  0…70 | 
|  Medium temperature short time [°C] |  0…90; (< 1 h) | 
|  Water | 
|---|
|  Medium temperature [°C] |  0…35; (with climatic tube E43100: 35…65 °C) | 
|  Electrical data | 
|---|
|  Operating voltage [V] |  18…30 DC | 
|  Current consumption [mA] |  < 50 | 
|  Protection class |  III | 
|  Reverse polarity protection |  yes | 
|  Power-on delay time [s] |  < 3 | 
|  Inputs / outputs | 
|---|
|  Number of inputs and outputs |  Number of digital outputs: 2 | 
|  Outputs | 
|---|
|  Total number of outputs |  2 | 
|  Output signal |  switching signal; IO-Link | 
|  Electrical design |  PNP/NPN | 
|  Number of digital outputs |  2 | 
|  Output function |  normally open / normally closed; (parameterisable) | 
|  Max. voltage drop switching output DC [V] |  2.5 | 
|  Permanent current rating of switching output DC [mA] |  200 | 
|  Short-circuit protection |  yes | 
|  Type of short-circuit protection |  thermal, pulsed | 
|  Overload protection |  yes | 
|  Measuring/setting range | 
|---|
|  Factory setting |  hydrous coolants; water; media similar to water | 
|  Probe length L [mm] |  264 | 
|  Active range A [mm] |  195 | 
|  Inactive range I1 / I2 [mm] |  53 / 16 | 
|  Setting range | 
|---|
|  Set point SP [mm] |  25…200 | 
|  Reset point rP [mm] |  20…195 | 
|  In steps of [mm] |  5 | 
|  Reference point OP [mm] |  69 – 82 – 94 – 106 – 118 – 130 – 143 – 155 – 167 – 179 – 191 – 204 – OFF | 
|  Hysteresis, OP [mm] |  2 | 
|  Accuracy / deviations | 
|---|
|  Measuring error [% of the final value] |  ± 5 | 
|  Repeatability |  ± 2 | 
|  Resolution [mm] |  5 | 
|  Software / programming | 
|---|
|  Parameter setting options |  hysteresis / window; normally open / normally closed; switching logic; SP/rP position; adjustment OP; medium selection; offset setting; switch-on/switch-off delay | 
|  Interfaces | 
|---|
|  Communication interface |  IO-Link | 
|  Transmission type |  COM2 (38,4 kBaud) | 
|  IO-Link revision |  1.1 | 
|  SDCI standard |  IEC 61131-9 | 
|  Profiles |  Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | 
|  SIO mode |  yes | 
|  Required master port type |  A | 
|  Process data analogue |  2 | 
|  Process data binary |  2 | 
|  Min. process cycle time [ms] |  3.2 | 
|  Supported DeviceIDs | |  Type of operation |  DeviceID |  |  Default |  652 |  
  | 
|  Operating conditions | 
|---|
|  Ambient temperature [°C] |  0…60 | 
|  Storage temperature [°C] |  -25…80 | 
|  Protection |  IP 67 | 
|  Mechanical data | 
|---|
|  Weight [g] |  348.5 | 
|  Dimensions [mm] |  Ø 16 | 
|  Materials |  stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; NBR; PBT; PC; PA; PP; TPV | 
|  Materials (wetted parts) |  PP | 
|  Displays / operating elements | 
|---|
|  Display | |  Display unit |  2 x LED, green (cm, inch) |  |  switching status |  2 x LED, yellow |  |  measured values |  alphanumeric display, 4-digit |  |  parameter setting |  alphanumeric display, 4-digit |  
  | 
|  Remarks | 
|---|
|  Notes |  Please see the technical note under “Downloads” | 
|  Pack quantity |  1 pcs. | 
|  Electrical connection | 
|---|
|  Connection |  Connector: 1 x M12; Contacts: gold-plated |