| Product characteristics |
|---|
| Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
| Probe length L [mm] | 150…2000 |
| Process connection | G 3/4 external thread |
| Application |
|---|
| Special feature | Gold-plated contacts |
| Media | Liquids; oil-based media; hydrous media |
| Dielectric constant of the medium | ≥ 1,8; (for media with a dielectric constant of 1.8…5 (e.g. oils), a coaxial pipe is needed for operation) |
| Recommended media | water; hydrous media; oils; oil-based media |
| Medium temperature [°C] | -20…100 |
| Tank pressure [bar] | -1…16 |
| MAWP (for applications according to CRN) [bar] | 16 |
| Electrical data |
|---|
| Operating voltage [V] | 18…30 DC |
| Current consumption [mA] | < 50 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | < 3 |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
| Outputs |
|---|
| Total number of outputs | 2 |
| Output signal | switching signal; analogue signal; IO-Link |
| Electrical design | PNP/NPN |
| Number of digital outputs | 1 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] | 2.5 |
| Permanent current rating of switching output DC [mA] | 150; (200 (…60 °C)) |
| Number of analogue outputs | 1 |
| Analogue current output [mA] | 4…20, invertible; (scalable) |
| Max. load [Ω] | 500 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
| Measuring/setting range |
|---|
| Probe length L [mm] | 150…2000 |
| Active range A [mm] | L-40 (L-60); (when set to oil and oil based media) |
| Inactive range I1 / I2 [mm] | 30 / 10 (30); (when set to oil and oil based media) |
| Sampling rate [Hz] | 4 |
| Setting range |
|---|
| Set point SP [mm] | ≥ 15 (35) / ≤ L-30 |
| Note on setpoint SP | | when set to oil and oil based media |
|
| Reset point rP [mm] | ≥ 10 (30) / ≤ L-35 |
| Note on reset point rP | | when set to oil and oil based media |
|
| In steps of [mm] | 1 |
| Hysteresis [mm] | > 5 |
| Accuracy / deviations |
|---|
| Measuring error [mm] | ± 7 |
| Offset error [mm] | 5 |
| Resolution [mm] | 1 |
| Zero signal (current) [mA] | 4.0 |
| Full signal (current) [mA] | 20 |
| Temperature drift per 10 K | ± 0.2 % |
| Interfaces |
|---|
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 1 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 2.3 |
| Supported DeviceIDs | | Type of operation | DeviceID | | Default | 479 |
|
| Operating conditions |
|---|
| Ambient temperature [°C] | -40…80 |
| Storage temperature [°C] | -40…100 |
| Protection | IP 68; IP 69K |
| Mechanical data |
|---|
| Weight [g] | 447.5 |
| Materials | stainless steel (1.4404 / 316L); PEI; PFA; PBT; FKM |
| Materials (wetted parts) | stainless steel (1.4404 / 316L); stainless steel (1.4435 / 316L); PTFE; FKM |
| Process connection | G 3/4 external thread |
| Displays / operating elements |
|---|
| Display | | Display unit | 3 x LED, green | | switching status | 2 x LED, yellow | | level | alphanumeric display, 4-digit | | parameter setting | alphanumeric display, 4-digit |
|
| Remarks |
|---|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |