Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Factory setting | hydrous media; probe length L = 300 mm |
Probe length L [mm] | 100…1600 |
Process connection | G 3/4 external thread |
Application |
---|
Special feature | Gold-plated contacts |
Media | Liquids |
Dielectric constant of the medium | ≥ 1,8; (for media with a dielectric constant of 1.8…5 (e.g. oils), a coaxial pipe is needed for operation) |
Recommended media | water; hydrous media; oils; oil-based media |
Cannot be used for | See the operating instructions, chapter “Function and features”. |
Medium temperature [°C] | -25…80; (90 < 1 h) |
Tank pressure [bar] | -1…16 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC |
Current consumption [mA] | < 25 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | analogue signal; IO-Link |
Electrical design | PNP |
Number of digital outputs | 1 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20, invertible |
Max. load [Ω] | 500 |
Analogue voltage output [V] | 0…10, invertible |
Min. load resistance [Ω] | 2000 |
Short-circuit protection | yes |
Type of short-circuit protection | thermal, pulsed |
Overload protection | yes |
Measuring/setting range |
---|
Factory setting | hydrous media; probe length L = 300 mm |
Probe length L [mm] | 100…1600 |
Active range A [mm] | L-40; (when set to oil and oil based media: L-60) |
Inactive range I1 / I2 [mm] | 30 / 10; (when set to oil and oil based media: 30 / 30) |
Sampling rate [Hz] | 4 |
Accuracy / deviations |
---|
Repeatability [mm] | ± 5 |
Measuring error [mm] | ± 7 |
Offset error [mm] | 5 |
Resolution [mm] | 1 |
Zero signal (voltage) [V] | 0 |
Zero signal (current) [mA] | 4 |
Full signal (voltage) [V] | 10 |
Full signal (current) [mA] | 20 |
Temperature drift per 10 K | ± 0.2 % |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | no profile |
SIO mode | no |
Required master port type | A |
Process data analogue | 1 |
Min. process cycle time [ms] | 2.3 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 684 |
|
Operating conditions |
---|
Ambient temperature [°C] | -25…60 |
Storage temperature [°C] | -40…85 |
Protection | IP 68; IP 69K; (7 days / 1 m water depth / 0.1 bar: IP 68) |
Mechanical data |
---|
Weight [g] | 430 |
Materials | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; PEI |
Materials (wetted parts) | stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM; Sealing: NBR reinforced fibre |
Process connection | G 3/4 external thread |
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |