Product characteristics |
---|
Communication interface | IO-Link |
Laser protection class | 2 |
Housing | rectangular |
Dimensions [mm] | 59 x 42 x 52 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC |
Current consumption [mA] | < 150 |
Protection class | III |
Reverse polarity protection | yes |
Typ. lifetime [h] | 50000 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
---|
Total number of outputs | 2 |
Electrical design | PNP |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (programmable) |
Max. current load per output [mA] | 200 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20; (scalable IEC 61131-2) |
Max. load [Ω] | 250 |
Analogue voltage output [V] | 0…10; (scalable IEC 61131-2) |
Min. load resistance [Ω] | 5000 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Detection zone |
---|
Max. light spot width [mm] | 150 |
Max. light spot height [mm] | 150 |
Light spot dimensions refer to | 75 m |
Background suppression [m] | 75…150 |
Measuring/setting range |
---|
Measuring range [m] | 1…75; (Reflector E21159) |
Sampling rate [Hz] | 1…33 |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Smart Sensor: Sensor Identification; Binary Data Channel; Process Value; Sensor Diagnosis |
SIO mode | yes |
Required master port type | A |
Process data analogue | 1 |
Process data binary | 2 |
Min. process cycle time [ms] | 6 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 810 |
|
Operating conditions |
---|
Ambient temperature [°C] | -10…60 |
Protection | IP 67 |
Mechanical data |
---|
Weight [g] | 312 |
Housing | rectangular |
Dimensions [mm] | 59 x 42 x 52 |
Materials | housing: diecast zinc; front lens: glass; LED window: PC |
Lens alignment | side lens |
Displays / operating elements |
---|
Display | switching status | 2 x LED, yellow | operation | LED, green | distance value, programming | alphanumeric display, 4-digit |
|
Remarks |
---|
Remarks | operating voltage “supply class 2” according to cULus |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12 |
Other data |
---|
Parameter | Setting range | Factory setting | Uni | m, feet | m | OU1 | Hno, Hnc, Fno, Fnc | Hno | SP1 | 1.00…75.00 | 10.00 | nSP1 | 1.00…75.00 | 8.00 | FSP1 | 1.00…75.00 | 12.00 | OU2 | Hno, Hnc, Fno, Fnc, I, U | I | SP2 | 1.00…75.00 | 20.00 | nSP2 | 1.00…75.00 | 18.00 | FSP2 | 1.00…75.00 | 22.00 | ASP | 0…75.00 | 0 | AEP | 0…75.00 | 75.00 | rATE [Hz] | 1…33 | 15 | dS1 | 0…0.1…5 | 0 | dr1 | 0…0.1…5 | 0 | dS2 | 0…0.1…5 | 0 | dr2 | 0…0.1…5 | 0 | dFo | 0…0.1…5 | 0.2 | dIS | d1…3; rd1…3; OFF | d3 |
|
repeatability/accuracy |
---|
| repeatability of the measured values | Accuracy | 1…25 m | ± 15 mm | ± 35 mm | 30 m | ± 15 mm | ± 35 mm | 40 m | ± 15 mm | ± 35 mm | 50 m | ± 19 mm | ± 39 mm | 60 m | ± 27 mm | ± 47 mm | 70 m | ± 43 mm | ± 63 mm |
|
Sampling rate | | Reflector | 33 Hz |
|
repeatability/accuracy |
---|
| repeatability of the measured values | Accuracy | 1…75 m | ± 15 mm | ± 35 mm |
|
Sampling rate | | Reflector | 1 Hz | The values apply at | | Extraneous light on the object | < 100 klx | constant ambient conditions | 23 °C / 960 hPa | minimum power-on time in minutes | 10 |
|