Product characteristics |
---|
Communication interface | IO-Link |
Laser protection class | 2 |
Housing | rectangular |
Dimensions [mm] | 59 x 42 x 52 |
Application |
---|
Application [m] | 0.2…100 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC; (“supply class 2” to cULus) |
Current consumption [mA] | < 150 |
Protection class | III |
Reverse polarity protection | yes |
Typ. lifetime [h] | 50000 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
---|
Total number of outputs | 2 |
Electrical design | PNP |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (programmable) |
Max. current load per output [mA] | 200 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20; (IEC 61131-2) |
Max. load [Ω] | 250 |
Analogue voltage output [V] | 0…10; (IEC 61131-2) |
Min. load resistance [Ω] | 5000 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Detection zone |
---|
Max. light spot width [mm] | 25 |
Max. light spot height [mm] | 25 |
Light spot dimensions refer to | 18 m |
Background suppression [m] | < 100 |
Measuring/setting range |
---|
Measuring range [m] | 0.2…18; (white paper 200 x 200 mm 90% remission) |
Sampling rate [Hz] | 1…33 |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Smart Sensor: Sensor Identification; Binary Data Channel; Process Value; Sensor Diagnosis |
SIO mode | yes |
Required master port type | A |
Process data analogue | 2 |
Process data binary | 2 |
Min. process cycle time [ms] | 6 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 811 |
|
Operating conditions |
---|
Ambient temperature [°C] | -10…60 |
Protection | IP 67 |
Mechanical data |
---|
Weight [g] | 300.2 |
Housing | rectangular |
Dimensions [mm] | 59 x 42 x 52 |
Materials | housing: diecast zinc; front lens: glass; LED window: PC |
Lens alignment | side lens |
Displays / operating elements |
---|
Display | switching status | 2 x LED, yellow | operation | LED, green | distance value, programming | alphanumeric display, 4-digit |
|
Accessories |
---|
Accessories (optional) | |
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12 |
Other data |
---|
Parameter | Setting range | Factory setting | Uni | m, inch | m | OU1 | Hno, Hnc, Fno, Fnc | Hno | SP1 | 0.20…18.00 | 1.00 | nSP1 | 0.20…18.00 | 0.80 | FSP1 | 0.20…18.00 | 1.20 | OU2 | Hno, Hnc, Fno, Fnc, I, U | I | SP2 | 0.20…18.00 | 2.00 | nSP2 | 0.20…18.00 | 1.80 | FSP2 | 0.20…18.00 | 2.20 | ASP | 0…18.00 | 0 | AEP | 0…18.00 | 18.00 | rATE [Hz] | 1…33 | 15 | dS1 | 0…0.1…5 | 0 | dr1 | 0…0.1…5 | 0 | dS2 | 0…0.1…5 | 0 | dr2 | 0…0.1…5 | 0 | dFo | 0…0.1…5 | 0 | dIS | d1…3 ; rd1…3; OFF | d3 |
|
repeatability/accuracy |
---|
| repeatability of the measured values | | Accuracy | | | white (90 % remission) | grey (18 % remission) | white (90 % remission) | grey (18 % remission) | 0.20…1.0 m | ± 0.45 cm | ± 0.6 cm | ± 1.5 cm | ± 1.6 cm | 1.00…2.00 m | ± 0.5 cm | ± 0.8 cm | ± 1.5 cm | ± 1.8 cm | 2.00…4.00 m | ± 1.25 cm | ± 1.9 cm | ± 2.25 cm | ± 3.0 cm | 4.00…6.00 m | ± 2.0 cm | ± 3.0 cm | ± 3.0 cm | ± 4.0 cm | 6.00…10.00 m | ± 3.5 cm | ± 5.0 cm | ± 4.5 cm | ± 6.0 cm | 10.00…18.00 m | ± 5.0 cm | | ± 6.0 cm | |
|
Sampling rate | 15 Hz | Extraneous light on the object | < 10 klx | The values apply at | | constant ambient conditions | 23 °C / 960 hPa | minimum power-on time in minutes | 10 |
|
repeatability/accuracy |
---|
| repeatability of the measured values | | Accuracy | | | white (90 % remission) | grey (18 % remission) | white (90 % remission) | grey (18 % remission) | 0.20…1.0 m | ± 0.45 cm | ± 0.6 cm | ± 1.5 cm | ± 1.6 cm | 1.00…2.00 m | ± 0.5 cm | ± 0.8 cm | ± 1.5 cm | ± 1.8 cm | 2.00…4.00 m | ± 1.6 cm | ± 1.9 cm | ± 2.5 cm | ± 3.0 cm | 4.00…6.00 m | ± 2.4 cm | ± 3.3 cm | ± 3.5 cm | ± 4.5 cm | 6.00…10.00 m | ± 5.0 cm | | ± 6.5 cm | |
|
Sampling rate | 15 Hz | Extraneous light on the object | < 40 klx | The values apply at | | constant ambient conditions | 23 °C / 960 hPa | minimum power-on time in minutes | 10 |
|
In case of higher extraneous light on the object (up to 40 klx) the following specifications apply: |
---|
| white (90 % remission) | grey (18 % remission) | black (6 % remission) | | Measuring range | 0.2…10 m | 0.2…6 m | 0.2…4 m | |
|