| Product characteristics |
|---|
| Output signal | switching signal; analogue signal; IO-Link; (configurable) |
| Measuring range | | -0.05…1 bar | -50…1000 mbar | -0.73…14.5 psi | -5…100 kPa |
|
| Process connection | threaded connection G 1 external thread Aseptoflex Vario |
| Application |
|---|
| Special feature | Gold-plated contacts |
| Application | food and beverage industry |
| Media | viscous media and liquids with suspended particles; liquids and gases |
| Medium temperature [°C] | -25…125; (145 max. 1h) |
| Min. bursting pressure | | 30000 mbar | 435 psi | 3000 kPa |
|
| Pressure rating | | 10000 mbar | 145 psi | 1000 kPa |
|
| Vacuum resistance [mbar] | -1000 |
| Type of pressure | relative pressure |
| No dead space | yes |
| MAWP (for applications according to CRN) [bar] | 10 |
| Electrical data |
|---|
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Integrated watchdog | yes |
| 2-wire |
|---|
| Operating voltage [V] | 20…32 DC |
| Current consumption [mA] | 3.6…21 |
| Power-on delay time [s] | 1 |
| 3-wire |
|---|
| Operating voltage [V] | 18…32 DC |
| Current consumption [mA] | < 45 |
| Power-on delay time [s] | 0.5 |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Outputs |
|---|
| Total number of outputs | 2 |
| Output signal | switching signal; analogue signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Number of analogue outputs | 1 |
| Analogue current output [mA] | 4…20, invertible; (scalable) |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
| 2-wire |
|---|
| Max. load [Ω] | 300 |
| 3-wire |
|---|
| Max. voltage drop switching output DC [V] | 2 |
| Permanent current rating of switching output DC [mA] | 250 |
| Switching frequency DC [Hz] | 125 |
| Max. load [Ω] | (Ub – 10 V) / 20 mA |
| Measuring/setting range |
|---|
| Measuring range | | -0.05…1 bar | -50…1000 mbar | -0.73…14.5 psi | -5…100 kPa |
|
| Set point SP | | -48…1000 mbar | -0.7…14.5 psi | -4.8…100 kPa |
|
| Reset point rP | | -50…998 mbar | -0.73…14.47 psi | -0.5…99.8 kPa |
|
| Analogue start point | | -50…750 mbar | -0.73…10.88 psi | -5…75 kPa |
|
| Analogue end point | | 200…1000 mbar | 2.9…14.5 psi | 20…100 kPa |
|
| In steps of | |
| Factory setting | | SP1 = 250 mbar | rP1 = 230 mbar | | SP2 = 750 mbar | rP2 = 730 mbar | | ASP = 0 mbar | AEP = 1000 mbar |
|
| Accuracy / deviations |
|---|
| Switch point accuracy [% of the span] | < ± 0,2; (Turn down 1:1) |
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation [% of the span] | < ± 0,2; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) |
| Linearity deviation [% of the span] | < ± 0,15; (Turn down 1:1) |
| Hysteresis deviation [% of the span] | < ± 0,15; (Turn down 1:1) |
| Long-term stability [% of the span] | < ± 0,1; (Turn down 1:1; per year) |
| Temperature coefficient zero point [% of the span / 10 K] | < ± 0,05; (0…70 °C) |
| Temperature coefficient span [% of the span / 10 K] | < ± 0,15; (0…70 °C) |
| Response times |
|---|
| Damping for the switching output dAP [s] | 0…30 |
| Damping for the analogue output dAA [s] | 0.01…99.99 |
| 2-wire |
|---|
| Step response time analogue output [ms] | 45 |
| 3-wire |
|---|
| Min. response time of switching output (dAP) [ms] | 3 |
| Step response time analogue output [ms] | 7 |
| Interfaces |
|---|
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.0 |
| Profiles | no profile |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 1 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 2.3 |
| Supported DeviceIDs | | Type of operation | DeviceID | | Default | 256 |
|
| Operating conditions |
|---|
| Ambient temperature [°C] | -25…80 |
| Storage temperature [°C] | -40…100 |
| Protection | IP 67; IP 68; IP 69K |
| Mechanical data |
|---|
| Weight [g] | 359.6 |
| Materials | stainless steel (1.4404 / 316L); FKM; PTFE; PBT; PEI; PFA |
| Materials (wetted parts) | ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE |
| Min. pressure cycles | 100 million |
| Process connection | threaded connection G 1 external thread Aseptoflex Vario |
| Displays / operating elements |
|---|
| Display | | Display unit | LED, green | | switching status | LED, yellow | | function display | alphanumeric display, 4-digit | | measured values | alphanumeric display, 4-digit |
|
| Display unit | mbar; kPa; psi; inH2O; mWS; % of the span |
| Remarks |
|---|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |