Product characteristics
Output signal switching signal; analogue signal; IO-Link; (configurable)
Measuring range
-1…10 bar -14.6…145 psi -100…1000 kPa -0.1…1 MPa
Process connection threaded connection 1/4″ NPT internal thread
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature [°C] -25…80
Min. bursting pressure
150 bar 2175 psi 15 MPa
Pressure rating
75 bar 1087 psi 7.5 Mpa
Vacuum resistance [mbar] -1000
Type of pressure relative pressure; vacuum
MAWP (for applications according to CRN)
50 bar 725 psi 5 MPa
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 35
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 250
Switching frequency DC [Hz] < 500
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable 1:5)
Max. load [Ω] 500
Analogue voltage output [V] 0…10; (scalable 1:5)
Min. load resistance [Ω] 2000
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1…10 bar -14.6…145 psi -100…1000 kPa -0.1…1 MPa
Analogue start point
-1…8 bar -14.6…116 psi -0.1…0.8 MPa
Analogue end point
1…10 bar 14.6…145 psi 0.1…1 MPa
Factory setting / CMPT = 2
Set point SP
-0.94…10 bar -13.6…145 psi -0.094…1 MPa
Reset point rP
-0.98…9.96 bar -14.2…144.4 psi -0.098…0.996 MPa
Min. difference between SP and rP
0.06 bar 0.6 psi 0.006 MPa
In steps of
0.02 bar 0.2 psi 0.002 MPa
Status_B High Resolution / CMPT = 3
Set point SP
-0.94…10 bar -13.6…145 psi -0.094…1 MPa
Reset point rP
-0.98…9.96 bar -14.2…144.4 psi -0.098…0.996 MPa
Min. difference between SP and rP
0.06 bar 0.6 psi 0.005 MPa
In steps of
0.01 bar 0.1 psi 0.001 MPa
Accuracy / deviations
Notes on the accuracy / deviation switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1%
Switch point accuracy [% of the span] < ± 0,4; (Turn down 1:1)
Repeatability [% of the span] < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span] < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span] < ± 0,1; (Turn down 1:1)
Long-term stability [% of the span] < ± 0,05; (Turn down 1:1; per 6 months)
Temperature coefficient zero point [% of the span / 10 K] < ± 0,2; (-0…80 °C)
Temperature coefficient span [% of the span / 10 K] < ± 0,2; (-0…80 °C)
Response times
Response time [ms] < 1.5
Delay time programmable dS, dr [s] 0…50
Damping for the switching output dAP [s] 0…4
Damping for the analogue output dAA [s] 0…4
Max. response time analogue output [ms] 3
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode yes
Required master port type A; (wenn PIN 2 nicht verbunden: B)
Supported DeviceIDs
Type of operation DeviceID
Factory setting / CMPT = 2 473
Status_B High Resolution / CMPT = 3 989
Note
For further information please see the IODD PDF file under “Downloads”
Factory setting / CMPT = 2
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
Min. process cycle time [ms] 2.3
IO-Link resolution pressure [bar] 0.01
IO-Link process data (cyclical)
function bit length
pressure 14
binary switching information 2
IO-Link functions (acyclical) application specific tag
Status_B High Resolution / CMPT = 3
Profiles Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
Min. process cycle time [ms] 3
IO-Link resolution pressure [bar] 0.005
IO-Link process data (cyclical)
function bit length
pressure 14
device status 4
binary switching information 2
IO-Link functions (acyclical) application specific tag
Operating conditions
Ambient temperature [°C] -25…80
Storage temperature [°C] -40…100
Protection IP 65; IP 67
Mechanical data
Weight [g] 221.5
Materials stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (1.4404 / 316L); AI2O3 (96%; ceramics); FKM
Min. pressure cycles 100 million
Tightening torque [Nm] > 50; (depends on lubrication, seal and pressure rating)
Process connection threaded connection 1/4″ NPT internal thread
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
Display unit 3 x LED, green (bar, psi, MPa)
switching status 2 x LED, yellow
measured values alphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; Contacts: gold-plated

Thông tin bổ sung

Thương hiệu
Thời gian bảo hành

5 Năm

Điện áp ngõ vào
Ngõ ra

Analog, IO-Link, NC, NO, NPN, PNP

Cam kết và hỗ trợ

Luôn có giá tốt nhất thị trường
Giao hàng trên toàn quốc
Hỗ trợ dịch vụ kỹ thuật

Khu vực Miền Nam

Call: 0345 177768 / Chat Zalo zalo

Khu vực Miền Bắc

Call: 0384 988 968 / Chat Zalo zalo

Khu vực Miền Trung

Call: 0374 687 899 / Chat Zalo zalo

Dịch vụ kỹ thuật/Bảo hành

Call: 0348 957 778 / Chat Zalo zalo

Email liên hệ

Dịch vụ cung ứng sản phẩm

Vì sản phẩm đa dạng, nếu Quý khách chưa tìm được. Vui lòng liên hệ để được hỗ trợ.

Tư vấn lựa chọn hoặc chuyển đổi
Nhập khẩu thiết bị theo yêu cầu

dich-vu-sua-chua-bien-tan-thiet-bi-tu-dong-hoa