Product characteristics |
---|
Output signal | switching signal; IO-Link; (configurable) |
Measuring range | 0…100 bar | 0…1450 psi | 0…10 MPa |
|
Process connection | threaded connection 1/4″ NPT external thread |
Application |
---|
Special feature | Gold-plated contacts |
Measuring element | ceramic-capacitive pressure measuring cell |
Application | for industrial applications |
Media | Liquids |
Conditionally suitable for | use in gases at pressures > 25 bar only on request |
Medium temperature [°C] | -25…80 |
Min. bursting pressure | |
Pressure rating | |
Type of pressure | relative pressure |
MAWP (for applications according to CRN) [bar] | 125 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 35 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 0.3 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (200 (…60 °C) 250 (…40 °C)) |
Switching frequency DC [Hz] | < 170 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range |
---|
Measuring range | 0…100 bar | 0…1450 psi | 0…10 MPa |
|
Factory setting / CMPT = 2 |
---|
Set point SP | 1…100 bar | 10…1450 psi | 0.1…10 MPa |
|
Reset point rP | 0.5…99.5 bar | 5…1445 psi | 0.05…9.95 MPa |
|
Min. difference between SP and rP | |
In steps of | |
Status_B High Resolution / CMPT = 3 |
---|
Set point SP | 0.8…100 bar | 12…1450 psi | 0.08…10 MPa |
|
Reset point rP | 0.3…99.5 bar | 5…1443 psi | 0.03…9.95 MPa |
|
Min. difference between SP and rP | |
In steps of | |
Accuracy / deviations |
---|
Switch point accuracy [% of the span] | < ± 0,5 |
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] | < ± 0,25 |
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-0…80 °C) |
Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (-0…80 °C) |
Response times |
---|
Response time [ms] | < 3 |
Delay time programmable dS, dr [s] | 0…50 |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
SIO mode | yes |
Required master port type | A; (when pin 2 not connected: B) |
Supported DeviceIDs | Type of operation | DeviceID | Factory setting / CMPT = 2 | 452 | Status_B High Resolution / CMPT = 3 | 629 |
|
Note | For further information please see the IODD PDF file under “Downloads” |
|
Factory setting / CMPT = 2 |
---|
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
Min. process cycle time [ms] | 2.3 |
IO-Link resolution pressure [bar] | 0.1 |
IO-Link resolution pressure [MPa] | 0.01 |
IO-Link process data (cyclical) | function | bit length | pressure | 14 | binary switching information | 2 |
|
IO-Link functions (acyclical) | application specific tag |
Status_B High Resolution / CMPT = 3 |
---|
Profiles | Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
Min. process cycle time [ms] | 3 |
IO-Link resolution pressure [bar] | 0.05 |
IO-Link resolution pressure [MPa] | 0.005 |
IO-Link process data (cyclical) | function | bit length | pressure | 16 | device status | 4 | binary switching information | 2 |
|
IO-Link functions (acyclical) | application specific tag |
Operating conditions |
---|
Ambient temperature [°C] | -25…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 282 |
Materials | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) | stainless steel (1.4404 / 316L); ceramics; FKM |
Min. pressure cycles | 100 million |
Tightening torque [Nm] | 2…3 turns after hand-fastening; recommended tightening torque; depends on lubrication, seal and pressure rating |
Process connection | threaded connection 1/4″ NPT external thread |
Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements |
---|
Display | Display unit | 3 x LED, green (bar, psi, MPa) | switching status | 2 x LED, yellow | measured values | alphanumeric display, red/green 4-digit |
|
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |