Product characteristics |
---|
Output signal | switching signal; IO-Link; (configurable) |
Measuring range | 0…100 bar | 0…1450 psi | 0…10 MPa |
|
Process connection | flange internal thread:G 1/4; internal thread:M6 |
Application |
---|
Special feature | Gold-plated contacts |
Design | with flange adapter |
Media | liquids and gases |
Conditionally suitable for | use in gases at pressures > 25 bar only on request |
Medium temperature [°C] | -25…80 |
Min. bursting pressure | |
Pressure rating | |
Type of pressure | relative pressure |
Electrical data |
---|
Operating voltage [V] | 18…36 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 50 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Overvoltage protection | yes; (< 40 V) |
Power-on delay time [s] | 0.3 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 250 |
Switching frequency DC [Hz] | < 170 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Measuring/setting range |
---|
Measuring range | 0…100 bar | 0…1450 psi | 0…10 MPa |
|
Set point SP | 1…100 bar | 20…1450 psi | 0.1…10 MPa |
|
Reset point rP | 0.5…99.5 bar | 10…1440 psi | 0.05…9.95 MPa |
|
In steps of | |
Factory setting | | SP1 = 25.0 bar | rP1 = 23.0 bar | | SP2 = 75.0 bar | rP2 = 73.0 bar |
|
Accuracy / deviations |
---|
Switch point accuracy [% of the span] | < ± 0,5 |
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,5; (linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) |
Hysteresis deviation [% of the span] | < ± 0,25 |
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (-20…80 °C) |
Temperature coefficient span [% of the span / 10 K] | 0,2; (-20…80 °C) |
Response times |
---|
Delay time programmable dS, dr [s] | 0; 0,2…50 |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | no profile |
SIO mode | yes |
Required master port type | A |
Process data analogue | 1 |
Process data binary | 2 |
Min. process cycle time [ms] | 2.3 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 309 |
|
Operating conditions |
---|
Ambient temperature [°C] | -20…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 67 |
Mechanical data |
---|
Weight [g] | 381.5 |
Materials | stainless steel (1.4301 / 304); PC; PBT; PEI; FKM |
Materials (wetted parts) | steel (1.4104 / 430F); ceramics; FKM |
Min. pressure cycles | 100 million |
Process connection | flange internal thread:G 1/4; internal thread:M6 |
Restrictor element integrated | no |
Displays / operating elements |
---|
Display | Display unit | 3 x LED, green | switching status | 2 x LED, yellow | function display | alphanumeric display, 4-digit | measured values | alphanumeric display, 4-digit |
|
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection |
---|
| Connector: 1 x M12; Contacts: gold-plated |