Product characteristics |
---|
Output signal | switching signal; IO-Link; (configurable) |
Measuring range | 0…25 bar | 0…363 psi | 0…2.5 MPa |
|
Process connection | flange internal thread:G 1/4; internal thread:M6 |
Application |
---|
Special feature | Gold-plated contacts |
Design | with flange adapter |
Media | liquids and gases |
Medium temperature [°C] | -25…80 |
Min. bursting pressure | |
Pressure rating | |
Type of pressure | relative pressure |
Electrical data |
---|
Operating voltage [V] | 18…36 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 50 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Overvoltage protection | yes; (< 40 V) |
Power-on delay time [s] | 0.3 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 250 |
Switching frequency DC [Hz] | < 170 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Measuring/setting range |
---|
Measuring range | 0…25 bar | 0…363 psi | 0…2.5 MPa |
|
Set point SP | 0.2…25 bar | 4…362 psi | 0.02…2.5 MPa |
|
Reset point rP | 0.1…24.9 bar | 2…360 psi | 0.01…2.49 MPa |
|
In steps of | |
Factory setting | | SP1 = 6.3 bar | rP1 = 5.8 bar | | SP2 = 18.8 bar | rP2 = 18.3 bar |
|
Accuracy / deviations |
---|
Switch point accuracy [% of the final value] | < ± 0,5 |
Repeatability [% of the final value] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the final value] | < ± 0,5 |
Hysteresis deviation [% of the final value] | < ± 0,25 |
Long-term stability [% of the final value] | < ± 0,05 |
Response times |
---|
Delay time programmable dS, dr [s] | 0; 0,2…50 |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | no profile |
SIO mode | yes |
Required master port type | A |
Process data analogue | 1 |
Process data binary | 2 |
Min. process cycle time [ms] | 2.3 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 310 |
|
Operating conditions |
---|
Ambient temperature [°C] | -20…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 65 |
Mechanical data |
---|
Weight [g] | 370.5 |
Materials | stainless steel (1.4301 / 304); PC; PBT; PEI; FKM; PTFE |
Materials (wetted parts) | steel (1.4104 / 430F); ceramics; FKM |
Min. pressure cycles | 100 million |
Process connection | flange internal thread:G 1/4; internal thread:M6 |
Restrictor element integrated | no |
Displays / operating elements |
---|
Display | Display unit | 3 x LED, green | switching status | 2 x LED, yellow | function display | alphanumeric display, 4-digit | measured values | alphanumeric display, 4-digit |
|
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection |
---|
| Connector: 1 x M12; Contacts: gold-plated |