Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Process connection | diameter Ø 8 mm |
Application |
---|
Special feature | Gold-plated contacts |
Media | water; glycol solutions; air; oils |
Note on media | low-viscosity oils with viscosity: ≤ 40 mm²/s (40 °C) | high-viscosity oils with viscosity: > 40 mm²/s (40 °C) |
|
Medium temperature [°C] | -20…100 |
Pressure rating [bar] | 50 |
MAWP (for applications according to CRN) [bar] | 50 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC |
Current consumption [mA] | < 100 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 10 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; frequency signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 250 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20; (scalable) |
Max. load [Ω] | 350 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Frequency of the output [Hz] | 0…1000 |
Measuring/setting range |
---|
Probe length L [mm] | 100 |
Operating mode | relative; absolutely liquid; absolutely gaseous; (absolute: reference measurement recommended) |
Note on factory setting | |
Liquids |
---|
Setting range [m/s] | 0.04…6 |
Greatest sensitivity [m/s] | 0.04…3 |
Gases |
---|
Setting range [m/s] | 0…200 |
Greatest sensitivity [m/s] | 2…100 |
Temperature monitoring |
---|
Measuring range [°C] | -20…100 |
Resolution [°C] | 0.2 |
Accuracy / deviations |
---|
Flow monitoring |
---|
Temperature drift [cm/s x 1/K] | 0,003 m/s x 1/K (< 20 °C; > 70 °C) |
Temperature gradient [K/min] | 100 |
Accuracy | ± (7 % MW + 2 % MEW); (for relative mode in the range of maximum sensitivity under the following conditions :; water: 20…70 °C; inlet length: 1.5 m; DN25 (DIN 2448); mounting position according to instructions; Accuracy can differ for other media and mounting positions.) |
Repeatability | 0,05 m/s; (water; flow velocity: 0,05…3 m/s) |
Temperature monitoring |
---|
Temperature drift | ± 0,005 K/°C |
Accuracy [K] | ± 0,3 / ± 1; (water; flow velocity: 0,3…3 m/s / air; flow velocity: > 10 m/s) |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 0.5; (T09; water; glycol: 0,8 s; air: 7 s; oil: 1,8 s; each T09) |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | 1,5 (T09); (water; flow velocity: 0,3…3 m/s) |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode | yes |
Required master port type | A |
Process data analogue | 2 |
Process data binary | 2 |
Min. process cycle time [ms] | 3 |
Supported DeviceIDs | Type of operation | DeviceID | Factory setting / ModE = (REL) | 533 | ModE = (LIQU) | 540 | ModE = (GAS) | 547 |
|
Operating conditions |
---|
Ambient temperature [°C] | -40…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 299.5 |
Materials | stainless steel (1.4404 / 316L); PBT-GF20; PBT-GF30 |
Materials (wetted parts) | stainless steel (1.4404 / 316L) |
Process connection | diameter Ø 8 mm |
Displays / operating elements |
---|
Display | Display unit | 6 x LED, green (%, m/s, l/min, m³/h, °C, 10³) | switching status | 2 x LED, yellow | measured values | alphanumeric display, red/green 4-digit |
|
Remarks |
---|
Remarks | MW = measured value | MEW = Final value of the measuring range |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |