Product characteristics |
---|
Measuring range | 2…100 l/min | 0.12…6 m³/h | 32…1586 gph | 0.55…26.4 gpm |
|
Process connection | threaded connection G 1 internal thread |
Application |
---|
Special feature | Gold-plated contacts |
Media | Liquids; oil |
Note on media | oil with viscosity: 10 mm²/s (40 °C) |
|
Medium temperature [°C] | -10…100 |
Pressure rating [bar] | 100 |
Pressure rating [Mpa] | 10 |
Note on pressure rating | at medium temperature >70°C: 80 bar / 8 MPa |
|
Electrical data |
---|
Operating voltage [V] | 18…30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; frequency signal; IO-Link |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Max. current load per output [mA] | 150; (200: …60 °C; Ambient temperature; 250: …40 °C; Ambient temperature) |
Analogue current output [mA] | 4…20 |
Max. load [Ω] | 500 |
Short-circuit protection | yes |
Overload protection | yes |
Frequency of the output [Hz] | 0…10000 |
Measuring/setting range |
---|
Measuring range | 2…100 l/min | 0.12…6 m³/h | 32…1586 gph | 0.55…26.4 gpm |
|
Display range | 0…120 l/min | 0…7.2 m³/h | 0…1902 gph | 0…31.7 gpm |
|
Resolution | 0.1 l/min | 0.01 m³/h | 1 gph | 0.01 gpm |
|
Set point SP | 0.7…100 l/min | 0.04…6 m³/h | 10…1586 gph | 0.15…26.4 gpm |
|
Reset point rP | 0…99.3 l/min | 0…5.96 m³/h | 0…1574 gph | 0…26.25 gpm |
|
Frequency end point, FEP | 6.7…100 l/min | 0.4…6 m³/h | 106…1586 gph | 1.75…26.4 gpm |
|
In steps of | 0.1 l/min | 0.01 m³/h | 2 gph | 0.05 gpm |
|
Frequency at the end point FRP [Hz] | 10…10000 |
In steps of [Hz] | 10 |
Measuring dynamics | 1:50 |
In steps of | 10 Hz |
Temperature monitoring |
---|
Measuring range | |
Display range | -32…122 °C | -25.6…251.6 °F |
|
Resolution | |
Set point SP | |
Reset point rP | |
In steps of | |
Frequency start point, FSP | |
Frequency end point, FEP | |
Frequency at the end point FRP [Hz] | 10…10000 |
Accuracy / deviations |
---|
Flow monitoring |
---|
Accuracy (in the measuring range) | ± 5 % MEW; (Q > 1 l/min; 20…70 °C Medium temperature) |
Repeatability | ± 1 % MEW |
Temperature monitoring |
---|
Temperature drift | 0,029 °C / K |
Accuracy [K] | 3 K (25°C; Q > 1 l/min) |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 0.01 |
Damping for the switching output dAP [s] | 0…5 |
In steps of [s] | 0.1 |
Damping for the analogue output dAA [s] | 0…5 |
In steps of [s] | 0.1 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 120 (Q > 1 l/min) |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current/frequency output; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour; calibration factor |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode | yes |
Required master port type | A |
Process data analogue | 2 |
Process data binary | 2 |
Min. process cycle time [ms] | 3.2 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 1046 |
|
Operating conditions |
---|
Ambient temperature [°C] | 0…60 |
Note on ambient temperature | medium temperature < 80 °C | medium temperature < 100 °C: 0…40 °C |
|
Storage temperature [°C] | -15…80 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 1586.5 |
Materials | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC; brass chemically nickel-plated |
Materials (wetted parts) | stainless steel (1.4401 / 316); stainless steel (1.4404 / 316L); brass (2.0371); brass chemically nickel-plated; PPS; O-ring: FKM |
Process connection | threaded connection G 1 internal thread |
Switching cycles mechanical | 10 million |
Displays / operating elements |
---|
Display | Display unit | 6 x LED, green | switching status | 2 x LED, yellow | measured values | alphanumeric display, red/green alternating indication 4-digit | programming | alphanumeric display, 4-digit |
|
Remarks |
---|
Remarks | Recommendation: use a 200-micron filter. | All data refer to oil with the following nominal viscosity: | 10 mm²/s, 40 °C | MW = measured value | MEW = Final value of the measuring range |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |