Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Process connection | threaded connection 3/4″ NPT |
Temperature monitoring |
---|
Measuring range [°F] | 14…212 |
Application |
---|
Special feature | Gold-plated contacts |
Application | for industrial applications |
Media | water; glycol solutions; coolants; oil |
Note on media | oil 1 with viscosity: 10 mm²/s (40 °C) | oil 2 with viscosity: 46 mm²/s (40 °C) |
|
Medium temperature [°F] | 14…212 |
Pressure rating [bar] | 40 |
Pressure rating [Mpa] | 4 |
MAWP (for applications according to CRN) [bar] | 40 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; frequency signal; IO-Link; (configurable) |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 150; (per output 2 x 200 (…60 °C); 2 x 250 (…40 °C)) |
Switching cycles (mechanical) | 10 million |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20 |
Max. load [Ω] | 500 |
Short-circuit protection | yes |
Overload protection | yes |
Frequency of the output [Hz] | 0…10000 |
Measuring/setting range |
---|
Measuring range | |
Display range | |
Resolution | |
Set point SP | |
Reset point rP | |
Frequency end point, FEP | |
In steps of | |
Frequency at the end point FRP [Hz] | 10…10000 |
Measuring dynamics | 1:50 |
Temperature monitoring |
---|
Measuring range [°F] | 14…212 |
Display range [°F] | -26…252 |
Resolution [°F] | 2 |
Set point SP [°F] | 16…212 |
Reset point rP [°F] | 14…210 |
In steps of [°F] | 2 |
Frequency start point, FSP [°F] | 14…172 |
Frequency end point, FEP [°F] | 54…212 |
Frequency at the end point FRP [Hz] | 10…10000 |
Accuracy / deviations |
---|
Flow monitoring |
---|
Accuracy (in the measuring range) | ± (4 % MW + 1 % MEW); (Q > 0,5 l/min; medium and operating temperature: +22 °C ± 4K) |
Repeatability | ± 1 % MEW |
Temperature monitoring |
---|
Temperature drift | 0,029 °C / K |
Accuracy [K] | 3 K (25°C; Q > 1 l/min) |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 0.01 |
Damping for the switching output dAP [s] | 0…5 |
Damping for the analogue output dAA [s] | 0…5 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 120 (Q > 1 l/min) |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current output; medium selection; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | Smart Sensor: Process Data Variable; Device Identification |
SIO mode | yes |
Required master port type | A |
Process data analogue | 2 |
Process data binary | 2 |
Min. process cycle time [ms] | 5 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 566 |
|
Operating conditions |
---|
Ambient temperature [°F] | 32…140 |
Note on ambient temperature | medium temperature < 176 °F | medium temperature < 212 °F: 32…104 °F |
|
Storage temperature [°F] | 5…176 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 691.5 |
Materials | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC; brass chemically nickel-plated |
Materials (wetted parts) | stainless steel (1.4401 / 316); stainless steel (1.4404 / 316L); brass (2.0371); brass chemically nickel-plated; PPS; O-ring: FKM |
Process connection | threaded connection 3/4″ NPT |
Displays / operating elements |
---|
Display | Display unit | 3 x LED, green | switching status | 2 x LED, yellow | measured values | alphanumeric display, red/green 4-digit | programming | alphanumeric display, 4-digit |
|
Remarks |
---|
Remarks | Recommendation: use a 200-micron filter. | All data refer to water (68 °F). | MW = measured value | MEW = Final value of the measuring range |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |