Product characteristics | |||||
---|---|---|---|---|---|
Number of inputs and outputs | Number of digital outputs: 2 | ||||
Process connection | M18 x 1,5 internal thread | ||||
Application | |||||
Media | Liquids; Gases | ||||
Medium temperature [°C] | -25…80 | ||||
Pressure rating [bar] | 300 | ||||
Liquids | |||||
Medium temperature [°C] | -25…80 | ||||
Gases | |||||
Medium temperature [°C] | -25…80 | ||||
Electrical data | |||||
Operating voltage [V] | 18…36 DC | ||||
Current consumption [mA] | < 60 | ||||
Protection class | III | ||||
Reverse polarity protection | yes | ||||
Power-on delay time [s] | 10 | ||||
Inputs / outputs | |||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||
Outputs | |||||
Total number of outputs | 2 | ||||
Output signal | switching signal; IO-Link; (configurable) | ||||
Electrical design | PNP | ||||
Number of digital outputs | 2 | ||||
Output function | normally open / normally closed; (parameterisable) | ||||
Max. voltage drop switching output DC [V] | 2.5 | ||||
Permanent current rating of switching output DC [mA] | 250 | ||||
Short-circuit protection | yes | ||||
Type of short-circuit protection | pulsed | ||||
Overload protection | yes | ||||
Measuring/setting range | |||||
Probe length L [mm] | 45 | ||||
Liquids | |||||
Setting range [cm/s] | 3…300 | ||||
Greatest sensitivity [cm/s] | 3…100 | ||||
Gases | |||||
Setting range [cm/s] | 200…3000 | ||||
Greatest sensitivity [cm/s] | 200…800 | ||||
Accuracy / deviations | |||||
Repeatability [cm/s] | 1…5 | ||||
Note on repeatability |
| ||||
Temperature drift [cm/s x 1/K] | 0.1; (for water 5…100 cm/s; 10…70 °C) | ||||
Temperature gradient [K/min] | 300 | ||||
Switch point accuracy [cm/s] | ± 2…± 10; (for water 5…100 cm/s; 25 °C; Factory setting) | ||||
Hysteresis [cm/s] | 2…5; (for water 5…100 cm/s; 25 °C; Factory setting) | ||||
Response times | |||||
Response time [s] | 1…10 | ||||
Liquids | |||||
Response time [s] | 1…10 | ||||
Gases | |||||
Response time [s] | 1…10 | ||||
Software / programming | |||||
Adjustment of the switch point | pushbutton | ||||
Interfaces | |||||
Communication interface | IO-Link | ||||
Transmission type | COM2 (38,4 kBaud) | ||||
IO-Link revision | 1.1 | ||||
SDCI standard | IEC 61131-9 | ||||
Profiles | Smart Sensor: Process Data Variable; Device Identification | ||||
SIO mode | yes | ||||
Required master port type | A | ||||
Process data analogue | 2 | ||||
Process data binary | 2 | ||||
Min. process cycle time [ms] | 3 | ||||
Supported DeviceIDs |
| ||||
Operating conditions | |||||
Ambient temperature [°C] | -25…80 | ||||
Storage temperature [°C] | -25…100 | ||||
Protection | IP 65; IP 67 | ||||
Mechanical data | |||||
Weight [g] | 247.5 | ||||
Dimensions [mm] | M18 x 1.5 | ||||
Thread designation | M18 x 1.5 | ||||
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PC; PBT-GF20; EPDM/X | ||||
Materials (wetted parts) | stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A | ||||
Process connection | M18 x 1,5 internal thread | ||||
Displays / operating elements | |||||
Display |
| ||||
Remarks | |||||
Pack quantity | 1 pcs. | ||||
Electrical connection | |||||
Connection | Connector: 1 x M12 |
Cảm biến lưu lượng IFM SI5002 300 bar
11.181.000 ₫
SKU: SI5002
Hãng sản xuất: IFM
Chất lượng: Mới 100%
Bảo hành: Chính hãng
Chứng từ: CO/CQ, hóa đơn VAT
Cam kết và hỗ trợ
Luôn có giá tốt nhất thị trường
Giao hàng trên toàn quốc
Hỗ trợ dịch vụ kỹ thuật
Khu vực Miền Nam
Khu vực Miền Bắc
Khu vực Miền Trung
Dịch vụ kỹ thuật/Bảo hành
Email liên hệ
Dịch vụ cung ứng sản phẩm
Vì sản phẩm đa dạng, nếu Quý khách chưa tìm được. Vui lòng liên hệ để được hỗ trợ.
Tư vấn lựa chọn hoặc chuyển đổi
Nhập khẩu thiết bị theo yêu cầu