Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range | |
Process connection | threaded connection G 2 DN50 flat seal |
Application |
---|
Special feature | Gold-plated contacts |
Application | totaliser function; empty pipe detection; for industrial applications |
Installation | connection to pipe by means of an adapter |
Media | conductive liquids; water; hydrous media |
Note on media | conductivity: ≥ 20 µS/cm | viscosity: < 70 mm²/s (40 °C) |
|
Medium temperature [°C] | -10…70 |
Pressure rating [bar] | 16 |
Pressure rating [Mpa] | 1.6 |
MAWP (for applications according to CRN) [bar] | 16.5 |
Electrical data |
---|
Operating voltage [V] | 18…32 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 150 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 5 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Inputs |
---|
Inputs | counter reset |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; pulse signal; frequency signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 250; (per output) |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20; (scalable) |
Max. load [Ω] | 500 |
Analogue voltage output [V] | 0…10; (scalable) |
Min. load resistance [Ω] | 2000 |
Pulse output | flow rate meter |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Frequency of the output [Hz] | 0.1…10000 |
Measuring/setting range |
---|
Measuring range | |
Display range | -720…720 l/min | -43.2…43.2 m³/h |
|
Resolution | |
Set point SP | |
Reset point rP | 5…597 l/min | 0.3…35.8 m³/h |
|
Analogue start point ASP | |
Analogue end point AEP | 120…600 l/min | 7.2…36 m³/h |
|
Low flow cut-off LFC | |
In steps of | |
Measuring dynamics | 1:120 |
Volumetric flow quantity monitoring |
---|
Pulse value | 0.0001…600 x 10³ m³ |
In steps of | 0.0001 m³ |
Pulse length [s] | 0,008…2 |
Temperature monitoring |
---|
Measuring range [°C] | -20…80 |
Display range [°C] | -40…100 |
Resolution [°C] | 0.2 |
Set point SP [°C] | -19.2…80 |
Reset point rP [°C] | -19.6…79.6 |
Analogue start point [°C] | -20…60 |
Analogue end point [°C] | 0…80 |
In steps of [°C] | 0.2 |
Accuracy / deviations |
---|
Flow monitoring |
---|
Accuracy (in the measuring range) | ± (0,8 % MW + 0,5 % MEW) |
Repeatability | ± 0,2% MEW |
Temperature monitoring |
---|
Temperature drift | ± 0,0333 °C / K |
Accuracy [K] | ± 1 (bei 25 °C, Q > 15 l/min) |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 0.35; (dAP = 0) |
Delay time programmable dS, dr [s] | 0…50 |
Damping for the switching output dAP [s] | 0…5 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 3 (Q > 15 l/min) |
Software / programming |
---|
Parameter setting options | Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/frequency/pulse output; start-up delay; display can be deactivated; Display unit; empty pipe detection |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | Smart Sensor: Process Data Variable; Device Identification |
SIO mode | yes |
Required master port type | A |
Process data analogue | 3 |
Process data binary | 2 |
Min. process cycle time [ms] | 5 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 357 |
|
Operating conditions |
---|
Ambient temperature [°C] | -10…60 |
Storage temperature [°C] | -25…80 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 3163 |
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U |
Materials (wetted parts) | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Centellen; EPDM |
Process connection | threaded connection G 2 DN50 flat seal |
Displays / operating elements |
---|
Display | Display unit | 6 x LED, green (l/min, m³/h, l, m³, 10³, °C) | switching status | 2 x LED, yellow | measured values | alphanumeric display, 4-digit | programming | alphanumeric display, 4-digit |
|
Accessories |
---|
Accessories (supplied) | sealings: 2, Centellen | Label |
|
Remarks |
---|
Remarks | MW = measured value | MEW = Final value of the measuring range |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |