Cảm biến lưu lượng IFM SM9001 16 bar

29.714.000 

SKU: SM9001
Hãng sản xuất: IFM
Chất lượng: Mới 100%
Bảo hành: Chính hãng
Chứng từ: CO/CQ, hóa đơn VAT

Báo giá
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
80…4800 gph 1.3…80 gpm
Process connection threaded connection G 2 DN50 flat seal
Application
Special feature Gold-plated contacts
Application totaliser function; empty pipe detection; for industrial applications
Installation connection to pipe by means of an adapter
Media conductive liquids; water; hydrous media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°F] 14…158
Pressure rating [bar] 16
MAWP (for applications according to CRN) [bar] 16.5
Electrical data
Operating voltage [V] 18…32 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 150
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 5
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputs counter reset
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; pulse signal; frequency signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 250; (per output)
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable)
Max. load [Ω] 500
Analogue voltage output [V] 0…10; (scalable)
Min. load resistance [Ω] 2000
Pulse output flow rate meter
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Frequency of the output [Hz] 0.1…10000
Measuring/setting range
Measuring range
80…4800 gph 1.3…80 gpm
Display range
-5760…5760 gph -96…96 gpm
Resolution
5 gph 0.1 gpm
Set point SP
105…4800 gph 1.7…80 gpm
Reset point rP
80…4775 gph 1.3…79.6 gpm
Analogue start point ASP
0…3840 gph 0…64 gpm
Analogue end point AEP
960…4800 gph 16…80 gpm
Low flow cut-off LFC
< 240 gph < 4 gpm
In steps of
5 gph 0.1 gpm
Measuring dynamics 1:60
Volumetric flow quantity monitoring
Pulse value 0.02…80 E06 gal
In steps of 0.02 gal
Pulse length [s] 0,016…2
Temperature monitoring
Measuring range [°F] -4…176
Display range [°F] -40…212
Resolution [°F] 0.5
Set point SP [°F] -2…176
Reset point rP [°F] -3…175
Analogue start point [°F] -4…140
Analogue end point [°F] 32…176
In steps of [°F] 0.5
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range) ± (0,8 % MW + 0,5 % MEW)
Repeatability ± 0,2% MEW
Temperature monitoring
Temperature drift ± 0,0185 °F / K
Accuracy [K] ± 1 (77 °F; Q > 4 gpm)
Response times
Flow monitoring
Response time [s] 0.35; (dAP = 0)
Delay time programmable dS, dr [s] 0…50
Damping for the switching output dAP [s] 0…5
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 3 (Q > 4 gpm)
Software / programming
Parameter setting options Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/frequency/pulse output; start-up delay; display can be deactivated; Display unit; empty pipe detection
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles Smart Sensor: Process Data Variable; Device Identification
SIO mode yes
Required master port type A
Process data analogue 3
Process data binary 2
Min. process cycle time [ms] 5
Supported DeviceIDs
Type of operation DeviceID
Default 392
Operating conditions
Ambient temperature [°F] 14…140
Storage temperature [°F] -13…176
Protection IP 65; IP 67
Mechanical data
Weight [g] 3163
Materials stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U
Materials (wetted parts) stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Centellen; FKM
Process connection threaded connection G 2 DN50 flat seal
Displays / operating elements
Display
Display unit 6 x LED, green (gpm, gph, gal, °F, 10³, 1000 x 10³)
switching status 2 x LED, yellow
measured values alphanumeric display, 4-digit
programming alphanumeric display, 4-digit
Accessories
Accessories (supplied)
sealings: 2, Centellen
Label
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; Contacts: gold-plated

Thông tin bổ sung

Thương hiệu
Thời gian bảo hành

5 Năm

Điện áp ngõ vào
Ngõ ra

Analog, NC, NO, NPN, PNP

Yêu cầu tư vấn0342 678 887(Call/Zalo)

Khu vực Miền Nam

Call: 0345 177 768 / Chat Zalo zalo

Khu vực Miền Bắc

Call: 0384 988 968 / Chat Zalo zalo

Khu vực Miền Trung

Call: 0374 687 899/ Chat Zalo zalo

Dịch vụ kỹ thuật/Bảo hành

Call: 0348 957 778/ Chat Zalo zalo

Email liên hệ

dich-vu-sua-chua-bien-tan-thiet-bi-tu-dong-hoa