Product characteristics |
---|
Number of inputs and outputs | Number of analogue outputs: 2 |
Measuring range | 5…300 l/min | 0.3…18 m³/h | 80…4755 gph | 1.3…79.3 gpm |
|
Process connection | threaded connection G 2 DN50 flat seal |
Application |
---|
Special feature | Gold-plated contacts |
Application | empty pipe detection; for industrial applications |
Installation | connection to pipe by means of an adapter |
Media | conductive liquids; water; hydrous media |
Note on media | conductivity: ≥ 20 µS/cm | viscosity: < 70 mm²/s (40 °C) |
|
Medium temperature | |
Pressure rating [bar] | 16 |
Pressure rating [Mpa] | 1.6 |
Pressure rating [psi] | 232 |
MAWP (for applications according to CRN) [bar] | 16.5 |
Electrical data |
---|
Operating voltage [V] | 18…32 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 150 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 5 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of analogue outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | analogue signal |
Number of analogue outputs | 2 |
Analogue current output [mA] | 4…20; (≤ 22 mA; scalable) |
Max. load [Ω] | 500 |
Measuring/setting range |
---|
Measuring range | 5…300 l/min | 0.3…18 m³/h | 80…4755 gph | 1.3…79.3 gpm |
|
Display range | -360…360 l/min | -21.6…21.6 m³/h | -5705…5705 gph | -95.1…95.1 gpm |
|
Resolution | 0.5 l/min | 0.02 m³/h | 5 gph | 0.1 gpm |
|
Analogue start point ASP | 0…240 l/min | 0…14.4 m³/h | 0…3800 gph | 0…63.4 gpm |
|
Analogue end point AEP | 60…300 l/min | 3.6…18 m³/h | 955…4755 gph | 15.9…79.3 gpm |
|
Low flow cut-off LFC | < 15 l/min | < 0.9 m³/h | < 240 gph | < 4 gpm |
|
In steps of | 0.5 l/min | 0.02 m³/h | 5 gph | 0.1 gpm |
|
Measuring dynamics | 1:60 |
Temperature monitoring |
---|
Measuring range | |
Display range | |
Resolution | |
Analogue start point | |
Analogue end point | |
In steps of | |
Accuracy / deviations |
---|
Flow monitoring |
---|
Accuracy (in the measuring range) | ± (0,8 % MW + 0,5 % MEW) |
Repeatability | ± 0,2% MEW |
Temperature monitoring |
---|
Temperature drift | ± 0,0333 °C / K; ± 0,0599 °F / K |
Accuracy [K] | ± 1 (25 °C; Q > 15 l/min) / ± 1 (77 °F; Q > 4 gpm) |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 0.35; (dAP = 0) |
Damping for the switching output dAP [s] | 0…5 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 3 (Q > 15 l/min) / T09 = 3 (Q > 4 gpm) |
Software / programming |
---|
Parameter setting options | display can be deactivated; Display unit; empty pipe detection |
Operating conditions |
---|
Ambient temperature | |
Storage temperature | |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 3140.5 |
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U |
Materials (wetted parts) | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Centellen; FKM |
Process connection | threaded connection G 2 DN50 flat seal |
Displays / operating elements |
---|
Display | Display unit | 6 x LED, green (l/min, m³/h, gpm, gph, °C, °F) | function display | 1 x LED, yellow (10³) | measured values | alphanumeric display, 4-digit | programming | alphanumeric display, 4-digit |
|
Display unit | l/min; m³/h; gpm; gph; °C; °F |
Accessories |
---|
Accessories (supplied) | sealings: 2, Centellen | Label |
|
Remarks |
---|
Remarks | MW = measured value | MEW = Final value of the measuring range |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |