Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Measuring range | |
Process connection | threaded connection G 3/4 flat seal |
Application |
---|
Special feature | Gold-plated contacts |
Application | for industrial applications |
Installation | connection to pipe by means of an adapter |
Media | water; glycol solutions; coolants; oil |
Note on media | low-viscosity oils with viscosity: 7…40 mm²/s (40 °C) | high-viscosity oils with viscosity: 30…68 mm²/s (40 °C) |
|
Medium temperature [°C] | -10…80 |
Pressure rating [bar] | 16 |
Pressure rating [Mpa] | 1.6 |
Electrical data |
---|
Operating voltage [V] | 19…30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | 100 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 10 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal |
Electrical design | PNP |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 250; (per output) |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range |
---|
Measuring range | |
Display range | |
Resolution | |
Set point SP | 0.1…50 l/min | 0.04…13.22 gpm |
|
Reset point rP | |
Max. flow rate [l/min] | 60 |
In steps of | |
Temperature monitoring |
---|
Measuring range [°C] | -10…80 |
Resolution [°C] | 0.2 |
Set point SP [°C] | -9.8…80 |
Reset point rP [°C] | -10…79.8 |
In steps of [°C] | 0.2 |
Accuracy / deviations |
---|
Flow monitoring |
---|
Accuracy (in the measuring range) | < ± (3 % MW + 0,2 % MEW) / < ± (5 % MW + 0,5 % MEW); (water; glycol: 35%; oil: viscosity 68 mm²/s at 40 °C) |
Repeatability | 0,1 l/min (0,025 gpm) |
Temperature monitoring |
---|
Accuracy [K] | 0,2 |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 0.25; (dAP = 0) |
Delay time programmable dS, dr [s] | 0…50 |
Damping for the switching output dAP [s] | 0…1 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 70 (Q > 5 l/min); (water) |
Software / programming |
---|
Parameter setting options | Flow monitoring; Temperature monitoring |
Operating conditions |
---|
Ambient temperature [°C] | -10…60 |
Storage temperature [°C] | -25…80 |
Protection | IP 67 |
Mechanical data |
---|
Weight [g] | 1535.5 |
Materials | housing: AlMgSi0,5 anodised; Sealing: FKM; connector housing: brass Optalloy-plated; PA 6.6; cover film: PA |
Materials (wetted parts) | stainless steel (1.4404 / 316L); FKM; PES; Centellen 200 |
Process connection | threaded connection G 3/4 flat seal |
Displays / operating elements |
---|
Display | Display unit | 4 x LED, green (l/min, m³/h, gal/min, gal/h) | Display unit | 2 x LED, yellow (°C / °F) | switching status | 2 x LED, yellow | measured values | alphanumeric display, 4-digit | programming | alphanumeric display, 4-digit |
|
Display unit | l/min; m³/h; gpm; gph; °C; °F |
Accessories |
---|
Accessories (supplied) | |
Accessories (optional) | adapter for pipe: 1 x R1/2, stainless steel, E40178 | adapter for pipe: 1 x 1/2″ NPT, stainless steel, E40191 | adapter for pipe: 1 x R1/2, brass, E40151 | adapter for pipe: 1 x 1/2″ NPT, brass, E40154 |
|
Remarks |
---|
Remarks | MW = measured value | MEW = Final value of the measuring range | sealing: only with supplied Centellen seals |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Moulded body: brass, Optalloy-plated; Contacts: gold-plated |