Product characteristics |
---|
Number of inputs and outputs | Number of analogue outputs: 1 |
Measuring range | |
Process connection | Clamp DN25…DN40 (1…1,5″) DIN 32676 (ISO 2852) |
Installation length EL [mm] | 30 |
Application |
---|
Measuring element | 1 x Pt 1000; (to DIN EN 60751, class A) |
Media | liquids and gases |
Pressure rating [bar] | 100 |
Vacuum resistance [mbar] | -1000 |
MAWP (for applications according to CRN) [bar] | 60 |
Electrical data |
---|
Operating voltage [V] | 18…32 DC; (“supply class 2” to cULus) |
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 2 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of analogue outputs: 1 |
Outputs |
---|
Total number of outputs | 1 |
Output signal | analogue signal; IO-Link; (configurable) |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20 |
Max. load [Ω] | 300 |
Short-circuit protection | yes |
Overload protection | yes |
Measuring/setting range |
---|
Measuring range | |
Factory setting | -10…150 °C |
Resolution |
---|
Resolution of analogue output [K] | 0.04 |
Resolution of display [K] | 0.1 |
Accuracy / deviations |
---|
Precision analogue output [K] | ± 0,3 + (± 0,1 % MS) |
Temperature coefficient [% of the span / 10 K] | 0,1; (in case of deviation from the reference condition 25 °C) |
Response times |
---|
Dynamic response T05 / T09 [s] | 1 / 3 |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
Operating conditions |
---|
Ambient temperature [°C] | -25…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 67; IP 68; IP 69K |
Mechanical data |
---|
Weight [g] | 331.5 |
Materials | stainless steel (1.4404 / 316L); PEI; FKM |
Materials (wetted parts) | stainless steel (1.4404 / 316L) electropolished |
Process connection | Clamp DN25…DN40 (1…1,5″) DIN 32676 (ISO 2852) |
Surface characteristics Ra/Rz of the wetted parts | Ra: < 0.8 |
Probe diameter [mm] | 6 |
Installation length EL [mm] | 30 |
Displays / operating elements |
---|
Display | | 7-segment LED display, 4-digit | | display unit / status, °C / °F |
|
Remarks |
---|
Remarks | MS = set measuring span | The values for accuracy apply to flowing water. |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12 |