| Product characteristics |
|---|
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | |
| Process connection | threaded connection Rc 1/2 internal thread DN10 |
| Application |
|---|
| Special feature | Gold-plated contacts |
| Application | for industrial applications |
| Media | water |
| Medium temperature [°C] | -10…90 |
| Pressure rating [bar] | 12 |
| Pressure rating [Mpa] | 1.2 |
| Note on pressure rating | |
| Electrical data |
|---|
| Operating voltage [V] | 18…30 DC |
| Current consumption [mA] | < 30 |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | < 3 |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital outputs: 2 |
| Outputs |
|---|
| Total number of outputs | 2 |
| Output signal | switching signal; frequency signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] | 2.5 |
| Permanent current rating of switching output DC [mA] | 100 |
| Short-circuit protection | yes |
| Overload protection | yes |
| Measuring/setting range |
|---|
| Measuring range | |
| Display range | |
| Resolution | |
| Set point SP | | 2.4…40 l/min | 0.14…2.4 m³/h |
|
| Reset point rP | | 2…39.6 l/min | 0.12…2.38 m³/h |
|
| Frequency end point, FEP | |
| In steps of | |
| Frequency at the end point FRP [Hz] | 100…1000 |
| Measuring dynamics | 1:20 |
| Temperature monitoring |
|---|
| Measuring range [°C] | -10…90 |
| Display range [°C] | -30…110 |
| Resolution [°C] | 0.5 |
| Set point SP [°C] | -9…90 |
| Reset point rP [°C] | -10…89 |
| In steps of [°C] | 0.5 |
| Frequency start point, FSP [°C] | -10…70 |
| Frequency end point, FEP [°C] | 10…90 |
| Frequency at the end point FRP [Hz] | 100…1000 |
| Accuracy / deviations |
|---|
| Flow monitoring |
|---|
| Accuracy (in the measuring range) | ± 2 % MEW |
| Repeatability | ± 0,5 % MEW |
| Temperature monitoring |
|---|
| Accuracy [K] | ± 1 |
| Response times |
|---|
| Flow monitoring |
|---|
| Response time [s] | 1; (dAP = 0) |
| Damping for the switching output dAP [s] | 0…5 |
| Temperature monitoring |
|---|
| Dynamic response T05 / T09 [s] | T09 = 6 |
| Software / programming |
|---|
| Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; frequency output; switch-on/switch-off delay; Damping; Display unit |
| Interfaces |
|---|
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 2 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 3 |
| Supported DeviceIDs | | Type of operation | DeviceID | | Default | 488 |
|
| Operating conditions |
|---|
| Ambient temperature [°C] | 0…60 |
| Note on ambient temperature | | medium temperature < 80 °C | | medium temperature < 90 °C: 0…50 °C |
|
| Storage temperature [°C] | -20…80 |
| Protection | IP 65; IP 67 |
| Mechanical data |
|---|
| Weight [g] | 441 |
| Materials | stainless steel (1.4404 / 316L); PC; PBT+PC-GF30; PPS; TPE-U |
| Materials (wetted parts) | stainless steel (1.4404 / 316L); ETFE; PA 6T; PPS; FKM |
| Tightening torque [Nm] | 30 |
| Process connection | threaded connection Rc 1/2 internal thread DN10 |
| Remarks |
|---|
| Remarks | | MW = measured value | | MEW = Final value of the measuring range |
|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |