Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Measuring range | |
Process connection | threaded connection 3/4″ NPT DN20 |
Application |
---|
Special feature | Gold-plated contacts |
Application | for industrial applications |
Media | water |
Medium temperature [°F] | 14…194 |
Pressure rating [bar] | 12 |
Pressure rating [psi] | 174 |
Note on pressure rating | |
MAWP (for applications according to CRN) [bar] | 4.3 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC |
Current consumption [mA] | < 30 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; frequency signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 100 |
Short-circuit protection | yes |
Overload protection | yes |
Measuring/setting range |
---|
Measuring range | |
Display range | |
Resolution | |
Set point SP | |
Reset point rP | |
Frequency end point, FEP | 315…1585 gph | 5.3…26.4 gpm |
|
In steps of | |
Frequency at the end point FRP [Hz] | 100…1000 |
Measuring dynamics | 1:20 |
Temperature monitoring |
---|
Measuring range [°F] | 14…194 |
Display range [°F] | -22…230 |
Resolution [°F] | 1 |
Set point SP [°F] | 16…194 |
Reset point rP [°F] | 14…192 |
In steps of [°F] | 1 |
Frequency start point, FSP [°F] | 14…158 |
Frequency end point, FEP [°F] | 50…194 |
Frequency at the end point FRP [Hz] | 100…1000 |
Accuracy / deviations |
---|
Flow monitoring |
---|
Accuracy (in the measuring range) | ± 2 % MEW |
Repeatability | ± 0,5 % MEW |
Temperature monitoring |
---|
Accuracy [K] | ± 1 |
Response times |
---|
Flow monitoring |
---|
Response time [s] | 1; (dAP = 0) |
Damping for the switching output dAP [s] | 0…5 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 6 |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; frequency output; switch-on/switch-off delay; Damping; Display unit |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode | yes |
Required master port type | A |
Process data analogue | 2 |
Process data binary | 2 |
Min. process cycle time [ms] | 3 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 494 |
|
Operating conditions |
---|
Ambient temperature [°F] | 32…140 |
Note on ambient temperature | medium temperature < 176 °F | medium temperature < 194 °F: 32…122 °F |
|
Storage temperature [°F] | -4…176 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 505.5 |
Materials | stainless steel (1.4404 / 316L); PC; PBT+PC-GF30; PPS; TPE-U |
Materials (wetted parts) | stainless steel (1.4404 / 316L); ETFE; PA 6T; PPS; FKM |
Tightening torque [Nm] | 30 |
Process connection | threaded connection 3/4″ NPT DN20 |
Remarks |
---|
Remarks | MW = measured value | MEW = Final value of the measuring range |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; Contacts: gold-plated |