Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range | 4…1250 l/min | 0.3…99.8 m/s | 0.25…75 m³/h |
|
Process connection | threaded connection R 1/2 DN15 |
Application |
---|
Application | for industrial applications |
Media | compressed air |
Medium temperature [°C] | -10…60 |
Min. bursting pressure [bar] | 64 |
Min. bursting pressure [MPa] | 6.4 |
Pressure rating [bar] | 16 |
Pressure rating [Mpa] | 1.6 |
Electrical data |
---|
Operating voltage [V] | 18…30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] | < 80 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 1 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Inputs |
---|
Inputs | counter reset |
Outputs |
---|
Output signal | switching signal; analogue signal; pulse signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (per output) |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20; (scalable) |
Max. load [Ω] | 500 |
Pulse output | consumed quantity meter |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range |
---|
Measuring range | 4…1250 l/min | 0.3…99.8 m/s | 0.25…75 m³/h |
|
Display range | 0…1500 l/min | 0…119.8 m/s | 0…90 m³/h |
|
Resolution | 1 l/min | 0.1 m/s | 0.05 m³/h |
|
Set point SP | 11…1250 l/min | 0.9…99.8 m/s | 0.65…74.97 m³/h |
|
Reset point rP | 5…1243 l/min | 0.4…99.3 m/s | 0.28…74.6 m³/h |
|
Analogue start point ASP | 0…1000 l/min | 0…79.8 m/s | 0…60 m³/h |
|
Analogue end point AEP | 250…1250 l/min | 20…99.8 m/s | 15…75 m³/h |
|
Low flow cut-off LFC | 1…13 l/min | 0.1…1.1 m/s | 0.09…0.8 m³/h |
|
In steps of | 1 l/min | 0.1 m/s | 0.01 m³/h |
|
Pressure monitoring |
---|
Measuring range [bar] | -1…16 |
Display range [bar] | -1…20 |
Resolution [bar] | 0.05 |
Set point SP [bar] | -0.92…16 |
Reset point rP [bar] | -1…15.92 |
Analogue start point [bar] | -1…12.8 |
Analogue end point [bar] | 2.2…16 |
In steps of [bar] | 0.01 |
Volumetric flow quantity monitoring |
---|
Measuring range | 0…100000000 m³ | 0…353146667.2 scf |
|
Display range | 0…100000000 m³ | 0…353146667.2 scf |
|
Set point SP | 0.001…10000000 m³ | 0.05…353146667.2 scf |
|
Pulse value | 0.001…10000000 m³ | 0.05…353146667.2 scf |
|
In steps of | |
Pulse length [s] | 0.002…2 |
Temperature monitoring |
---|
Measuring range | |
Display range | |
Resolution | |
Set point SP | |
Reset point rP | |
Analogue start point | |
Analogue end point | |
In steps of | |
Accuracy / deviations |
---|
Temperature coefficient [1/K] | ± 0,07 % MW |
Accuracy (in the measuring range) | class 141: ± (2 % MW + 0,5 % MEW); class 344: ± (6 % MW + 0,6 % MEW) ; air quality to ISO 8573-1:2010; at medium temperature 23 °C |
Repeatability | ± (0,4 % MW + 0,1 % MEW) |
Pressure monitoring |
---|
Repeatability [% of the final value] | ± 0,2 |
Characteristics deviation [% of the final value] | < ± 0,5; (BFSL = Best Fit Straight Line) |
Greatest TEMPCO of the span [% MEW / 10 K] | ± 0,15 |
Greatest TEMPCO of the zero point [% MEW / 10 K] | ± 0,25 |
Temperature monitoring |
---|
Accuracy [K] | ± 0,5; (medium flow in the limit area of the flow measurement range) |
Response times |
---|
Response time [s] | 0.1; (dAP = 0) |
Damping for the switching output dAP [s] | 0…5 |
Pressure monitoring |
---|
Response time [s] | 0.05 |
Temperature monitoring |
---|
Dynamic response T05 / T09 [s] | T09 = 0,5 |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; current/pulse output; display can be rotated and switched off; Display unit; totaliser |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 CDV |
Profiles | Digital Measuring Sensor (0x800A), Identification and Diagnosis (0x4000) |
SIO mode | yes |
Required master port type | A |
Process data analogue | 8 |
Process data binary | 2 |
Min. process cycle time [ms] | 7.2 |
Supported DeviceIDs | Type of operation | DeviceID | Default | 862 |
|
Operating conditions |
---|
Ambient temperature [°C] | 0…60 |
Storage temperature [°C] | -20…85 |
Max. relative air humidity [%] | 90 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 728.5 |
Materials | PBT+PC-GF30; PPS GF40; stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); steel (1.5523) galvanised; 2.0401 (brass / CW614N); FKM |
Materials (wetted parts) | stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); FKM; ceramics glass passivated; PPS GF40; Al2O3 (ceramics); acrylate |
Process connection | threaded connection R 1/2 DN15 |
Displays / operating elements |
---|
Display | | colour display 1,44″, 128 x 128 pixels | | 2 x LED, yellow |
|
Remarks |
---|
Remarks | MW = measured value | MEW = Final value of the measuring range | Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533. | For information about installation and operation please see the operating instructions. |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12 |