|  Electrical data | 
|---|
|  Frequency AC [Hz] |  47…64 | 
|  Operating voltage tolerance [%] |  15 | 
|  Nominal voltage AC [V] |  < 400 | 
|  Input voltage range AC [V] |  380…480 | 
|  Output voltage DC [V] |  24…28 | 
|  Protection class |  I; (IEC 61140) | 
|  Overvoltage protection |  yes; (< 35 DC) | 
|  Output voltage [V] |  adjustable; output voltage to SELV, PELV | 
|  Max. output current at min. output voltage [A] |  20 | 
|  Max. output current at max. output voltage [A] |  17.5 | 
|  Max. output current peak at min. output voltage [A] |  30 | 
|  Max. output current peak at max. output voltage [A] |  26 | 
|  Output power (permanent) [W] |  480 | 
|  Output power (peak) [W] |  720 | 
|  Note on output power (peak) | |  if consumption > 4 s the power is automatically reduced to the output power |  
  | 
|  Power factor (nominal voltage 400 V AC / 50 Hz) |  0.94 | 
|  Note on power factor (nominal voltage 400 V AC / 50 Hz) | |  with symmetrical phase voltage |  
  | 
|  Power factor (nominal voltage 480 V AC / 50 Hz) |  0.95 | 
|  Note on power factor (nominal voltage 480 V AC / 50 Hz) | |  with symmetrical phase voltage |  
  | 
|  Power reserve [%] |  50 | 
|  Number of output circuits |  1 | 
|  Max. residual ripple [mV] |  100 | 
|  Switch-on peak current (nominal voltage 400 V AC / 60 Hz) [A] |  3 | 
|  Switch-on peak current (nominal voltage 480 V AC / 50 Hz) [A] |  3 | 
|  Inrush current limitation |  yes | 
|  Efficiency (nominal voltage 400 V AC / 60 Hz) [%] |  95 | 
|  Efficiency (nominal voltage 480 V AC / 50 Hz) [%] |  94.8 | 
|  External input protection |  ≤ B-6 A / ≤ C-3 A | 
|  Derating [W/K] |  12 (60…70 °C) | 
|  Mains buffering time (nominal voltage 400 V AC / 60 Hz) [ms] |  22 | 
|  Mains buffering time (nominal voltage 480 V AC / 50 Hz) [ms] |  22 | 
|  Input current (nominal voltage 400 V AC / 60 Hz) [A] |  0.78 | 
|  Input current (nominal voltage 480 V AC / 50 Hz) [A] |  0.64 | 
|  Power loss (nominal voltage 400 V AC / 60 Hz) [W] |  25.3 | 
|  Power loss (nominal voltage 480 V AC / 50 Hz) [W] |  26.6 | 
|  Back feeding protection [V] |  34 | 
|  Outputs | 
|---|
|  Short-circuit proof |  yes | 
|  Overload protection |  yes | 
|  Overload performance |  output current constant | 
|  Type DC-OK signal |  relay output | 
|  Reliability of the DC OK signal |  60 V DC (0.3 A) / 30 V DC (1 A) / 30 V AC (0.5 A) | 
|  Operating conditions | 
|---|
|  Ambient temperature [°C] |  -25…70 | 
|  Note on ambient temperature | |  observe the free space for convection (see operating instructions) |  
  | 
|  Storage temperature [°C] |  -40…85 | 
|  Max. relative air humidity [%] |  95; (IEC 60068-2-30) | 
|  Protection |  IP 20; (EN 60529) | 
|  Degree of soiling |  2; (IEC 62103: conductive soiling not permitted) | 
|  Mechanical data | 
|---|
|  Weight [g] |  1029 | 
|  Type of mounting |  rail; (TH35 (EN 60715)) | 
|  Dimensions [mm] |  124 x 65 x 132.5 | 
|  Materials |  steel sheet | 
|  Displays / operating elements | 
|---|
|  Display | |  DC ok |  1 x LED |  |  overload |  1 x LED |  
  | 
|  Remarks | 
|---|
|  Remarks | |  Series connection of outputs only applies to identical units up to max. 150 V DC overall voltage |  
  | 
|  Pack quantity |  1 pcs. | 
|  Electrical connection | 
|---|
|  Connection |  screw terminals: |