Product characteristics |
---|
Output function | normally open / normally closed; (selectable) |
Sensing range [mm] | 4…24; (programming buttons) |
Housing | threaded type |
Dimensions [mm] | M18 x 1 / L = 87 |
Application |
---|
Installation | detection through non-metallic container wall or on bypass pipes |
Media | dry bulk material; liquids |
Recommended media | media with a dielectric constant < 20; oils |
Electrical data |
---|
Frequency AC [Hz] | 47…63 |
Operating voltage [V] | 30…250 AC / 20…250 DC |
Protection class | II |
Reverse polarity protection | yes |
Outputs |
---|
Output function | normally open / normally closed; (selectable) |
Max. voltage drop switching output DC [V] | 8 |
Max. voltage drop switching output AC [V] | 10 |
Max. leakage current [mA] | 2.5 (250 V AC) / 1.7 (110 V AC) / 1.5 (24 V DC) |
Permanent current rating of switching output AC [mA] | 100; (150 (…40 °C)) |
Permanent current rating of switching output DC [mA] | 100; (150 (…40 °C)) |
Short-time current rating of switching output [mA] | 1000; (20 ms / 0,5 Hz) |
Switching frequency AC [Hz] | 10 |
Switching frequency DC [Hz] | 10 |
Short-circuit proof | no |
Overload protection | no |
Detection zone |
---|
Sensing range [mm] | 4…24; (programming buttons) |
Sensing range adjustable | yes |
Factory setting sensing range [mm] | 12 |
Real sensing range Sr [mm] | 12 ± 10 % |
Accuracy / deviations |
---|
Correction factor | glass: 0.4 / water: 1 / ceramics: 0.2 / PVC: 0.1 |
Hysteresis [% of Sr] | 1…15 |
Switch point drift [% of Sr] | -20…20 |
Operating conditions |
---|
Ambient temperature [°C] | -25…80 |
Note on ambient temperature | temperature of the sensing face: -25…110 °C |
|
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 59.5 |
Housing | threaded type |
Mounting | non-flush mountable |
Dimensions [mm] | M18 x 1 / L = 87 |
Thread designation | M18 x 1 |
Materials | housing: PBT; plug: PC; pushbuttons: TPE-U |
Displays / operating elements |
---|
Display | switching status | 1 x LED ring, yellow plug lights translucently |
|
Electrical connection |
---|
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
Accessories |
---|
Accessories (supplied) | |
Remarks |
---|
Remarks | Note: | Check the safe functioning of the unit after a short circuit. |
|
Pack quantity | 1 pcs. |
Electrical connection – plug |
---|
| Connector: 1 x 1/2″ |