Product characteristics |
---|
Electrical design | PNP/NPN; (parameterisable) |
Communication interface | IO-Link |
Dimensions [mm] | 250 x 28 x 16.7 |
Application |
---|
Media | dry bulk material; aqueous solutions; oils |
Cannot be used for | highly adhesive media |
Electrical data |
---|
Operating voltage [V] | 10…30 DC; (IO-Link: 18…30 DC) |
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Max. power-on delay time [ms] | 1300 |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 3 |
Outputs |
---|
Electrical design | PNP/NPN; (parameterisable) |
Number of digital outputs | 3 |
Permanent current rating of switching output DC [mA] | 200 |
Max. resistance switching output [Ω] | 8 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Detection zone |
---|
Measuring range [mm] | < 200 |
Measuring/setting range |
---|
Detection range [mm] | 228 |
Set point SP [%] | 5…95 |
Reset point rP [%] | 4…94 |
In steps of [%] | 1 |
Accuracy / deviations |
---|
Repeatability [% of the final value] | 2 |
Offset deviation [% of the final value] | 4 |
Resolution [% of the final value] | 1 |
Linearity deviation [% of the final value] | 1 |
Response times |
---|
Response time [ms] | 1300 |
Software / programming |
---|
Parameter setting options | Damping; hysteresis / window; fault indication; diagnostic function; sensitivity; internal temperature; limitation of measuring range; adjustable switching delay; zero-point calibration; direction of installation; LEDs can be deactivated |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Digital Measuring Sensor Profile, Common Profile |
SIO mode | yes |
Required master port type | A |
Process data analogue | 1 |
Process data binary | 3 |
Min. process cycle time [ms] | 9.6 |
IO-Link process data (cyclical) | function | bit length | process value | 16 | exponent | 8 | device status | 4 | binary switching information | 3 |
|
IO-Link functions (acyclical) | direction of installation; limitation of sensor elements; sensitivity; minimum recognition threshold; Performance in case of a fault; error delay; Damping; LED_Modus; switch-on cycle counter; operating hours counter; switching cycles counter; min./max. process value; internal temperature; min./max. internal temperature; diagnostic data for level |
Supported DeviceIDs | Type of operation | DeviceID | Default | 924 |
|
Note | For further information please see the IODD PDF file under “Downloads” |
|
Operating conditions |
---|
Applications | DIN EN 60654-1 application class B2 |
Ambient temperature [°C] | -20…80 |
Storage temperature [°C] | -25…85 |
Protection | IP 65; IP 67 |
Mechanical data |
---|
Weight [g] | 377.5 |
Dimensions [mm] | 250 x 28 x 16.7 |
Materials | PBT; PC; |
Displays / operating elements |
---|
Display | operation | 1 x LED, green | switching status | 3 x LED, yellow | function | 20 x LED, green |
|
Accessories |
---|
Accessories (optional) | adhesive tape: 1 x 23 mm x 240 mm |
|
Remarks |
---|
Remarks | when used on IO-Link class B masters switching outputs OUT2, OUT3 have to be switched off |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12 |
Electrical connection – plug |
---|
| Cable: 0.1 m, PUR |