Product characteristics |
---|
Number of inputs and outputs | Number of analogue inputs: 4 |
Electrical data |
---|
Operating voltage [V] | 18…31.6 DC; (“supply class 2” to cULus) |
Max. current consumption from AS-i [mA] | 50 |
Reverse polarity protection | yes |
Max. current load total [A] | 2 |
Additional voltage supply [V] | 16…30 DC; (AUX) |
Inputs / outputs |
---|
Number of inputs and outputs | Number of analogue inputs: 4 |
Inputs |
---|
Number of analogue inputs | 4; (Anschluss von 2- und 3-Draht-Sensoren) |
Sensor supply of the inputs | AUX |
Analogue input (current) [mA] | 4…20 |
Max. voltage drop across load for nominal voltage [V] | 10 |
Analogue inputs protected against short circuits | yes |
Resolution of analogue input | 12 bit |
Accuracy / deviations |
---|
Measuring error [% of the final value] | 0,5 *) |
Operating conditions |
---|
Ambient temperature [°C] | -25…70 |
Protection | IP 67 |
AS-i classification |
---|
AS-i version | 2.11; 3.0 |
Extended addressing mode possible | no |
AS-i profile | S-7.3.E |
AS-i I/O configuration [hex] | 7 |
AS-i ID code [hex] | 3.E |
AS-i certificate | 123501 |
Mechanical data |
---|
Weight [g] | 188 |
Type of mounting | AS-i flat cables directly connectable |
Materials | PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
Displays / operating elements |
---|
Display | operation | LED, green Voltage AS-i | errors | LED, red | function | LED, yellow channels AI1…AI4 |
|
Accessories |
---|
Accessories (supplied) | |
Accessories (optional) | Protective cap: M12, E73004 |
|
Remarks |
---|
Remarks | There is an electrical separation between AS-i and AUX and between AS-i and the analogue inputs. | The actuator supply on pins 1 and 3 can be used to supply the sensors. |
|
Pack quantity | 1 pcs. |
Electrical connection |
---|
| quick mounting technology for AS-i flat cable: ; three orientations possible |
| Connector: M12 |