| Product characteristics |
|---|
| Number of inputs and outputs | Number of digital outputs: 2 |
| Factory setting | hydrous coolants; water; media similar to water |
| Probe length L [mm] | 472 |
| Application |
|---|
| Special feature | Gold-plated contacts |
| Media | hydrous coolants; oils; oil-based media; water; media similar to water |
| Dielectric constant of the medium | > 2 |
| Cannot be used for | extremely conductive media; adhering media; granulates; bulk material; acids; alkali; hygienic areas and electroplating applications |
| Tank pressure [bar] | 0.5; (unpressurized for applications to WHG (German Federal Water Act)) |
| Coolants |
|---|
| Medium temperature [°C] | 0…35; (with climatic tube E43101: 35…60 °C; not for applications to WHG (German Federal Water Act)) |
| Oil |
|---|
| Medium temperature [°C] | 0…70 |
| Medium temperature short time [°C] | 0…90; (< 1 h) |
| Maximum speed of the change of level [mm/s] | 200 |
| Water |
|---|
| Medium temperature [°C] | 0…35; (with climatic tube E43101: 35…60 °C; not for applications to WHG (German Federal Water Act)) |
| Electrical data |
|---|
| Operating voltage [V] | 12…30 DC |
| Current consumption [mA] | < 50 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | < 3 |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital outputs: 2 |
| Outputs |
|---|
| Total number of outputs | 2 |
| Output signal | switching signal; IO-Link |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Max. voltage drop switching output DC [V] | 2.5 |
| Permanent current rating of switching output DC [mA] | 200 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
| Measuring/setting range |
|---|
| Factory setting | hydrous coolants; water; media similar to water |
| Probe length L [mm] | 472 |
| Active range A [mm] | 390 |
| Inactive range I1 / I2 [mm] | 60 / 22 |
| Setting range |
|---|
| Set point SP [mm] | 35…390 |
| Reset point rP [mm] | 30…385 |
| In steps of [mm] | 5 |
| Reference point OP [mm] | 139 – 163 – 188 – 212 – 236 – 261 – 285 – 310 – 334 – 358 – 383 – 407 – OFF |
| Hysteresis, OP [mm] | 3 |
| Accuracy / deviations |
|---|
| Measuring error [% of the final value] | ± 5 |
| Repeatability | ± 2 |
| Resolution [mm] | 5 |
| Software / programming |
|---|
| Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; SP/rP position; adjustment OP; medium selection; offset setting; switch-on/switch-off delay |
| Interfaces |
|---|
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 3 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 3.2 |
| Supported DeviceIDs | | Type of operation | DeviceID | | Default | 803 |
|
| Operating conditions |
|---|
| Ambient temperature [°C] | 0…60 |
| Storage temperature [°C] | -25…80 |
| Protection | IP 67 |
| Mechanical data |
|---|
| Weight [g] | 450.9 |
| Dimensions [mm] | Ø 16 |
| Materials | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; NBR; PBT; PC; PA; PP; TPV |
| Materials (wetted parts) | PP |
| Displays / operating elements |
|---|
| Display | | Display unit | 2 x LED, green (cm, inch) | | switching status | 2 x LED, yellow | | measured values | alphanumeric display, 4-digit | | parameter setting | alphanumeric display, 4-digit |
|
| Remarks |
|---|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |