| Application | |||||||
|---|---|---|---|---|---|---|---|
| Application | Flow monitoring; Temperature monitoring; Wire monitoring | ||||||
| Electrical data | |||||||
| Operating voltage tolerance [%] | -20…10 | ||||||
| Operating voltage [V] | 24 DC | ||||||
| Current consumption [mA] | 90 | ||||||
| Protection class | III | ||||||
| Reverse polarity protection | no | ||||||
| Power-on delay time [s] | 10…80; (adjustable (fixed-value resistors terminals 22-23)) | ||||||
| Number of channels | 1 | ||||||
| Outputs | |||||||
| Performance in case of a fault | In case of undervoltage all relays are de-energised; the LED “LOW VOLTAGE/WIRE BREAK-RELAY” lights | ||||||
| Electrical design | relay | ||||||
| Contact rating | 4 A (250 V AC / 30 V DC) | ||||||
| Switching function flow monitoring | relay energised when flow is present and during the power-on delay time | ||||||
| Switching function temperature monitoring | relay energised when temperature is exceeded | ||||||
| Switching function wire break monitoring | relay de-energised in case of wire break or short circuit | ||||||
| Short-circuit proof | no | ||||||
| Overload protection | no | ||||||
| Response times | |||||||
| Response time [s] | < 3 | ||||||
| Software / programming | |||||||
| Adjustment of the switch point | potentiometer | ||||||
| Selection liquids / gases | wire bridge; on delivery: monitoring of liquids.; for monitoring of gases: link terminals 23 / 24. | ||||||
| Switch point setting | potentiometer | ||||||
| Temperature range [°C] | 40…120 | ||||||
| Repeatability of the set switch point [K] | 4 | ||||||
| Operating conditions | |||||||
| Ambient temperature [°C] | -20…60 | ||||||
| Note on ambient temperature |
| ||||||
| Protection | IP 20 | ||||||
| Mechanical data | |||||||
| Weight [g] | 234.5 | ||||||
| Housing | housing for DIN rail mounting | ||||||
| Dimensions [mm] | 100 x 25 x 103.5 | ||||||
| Materials | PBT | ||||||
| Displays / operating elements | |||||||
| Display |
| ||||||
| Electrical connection | |||||||
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting | ||||||
| Remarks | |||||||
| Remarks |
| ||||||
| Pack quantity | 1 pcs. | ||||||
| Electrical connection | |||||||
| Connection | COMBICON connector: | ||||||
Bộ điều khiển dòng chảy IFM SR0151
10.460.000 ₫
SKU: SR0151
Hãng sản xuất: IFM
Chất lượng: Mới 100%
Bảo hành: Chính hãng
Chứng từ: CO/CQ, hóa đơn VAT

Thông tin bổ sung
| Thương hiệu | |
|---|---|
| Thời gian bảo hành | 5 Năm |